GPH14H Technical Manual
PACKAGE HEAT PUMP SPECIFICATIONS
14
*PH1442H41E* *PH1448H41E* *PH1460H41E*
COOLING COOLING CAPACITY, BTUH 40,000 46,000 57,000
CAPACITY
SEER / EER 14.0 / 12.0 14.0 / 12.0 14.0 / 11.5
HEATING 47°/43°F 37,600 44,000 54,500
RATING 35°/33°F 27,500 32,000 43,000
17°/15°F 21,600 26,000 33,800
HSPF 8.0 8.0 8.0
UNIT VOLTAGE (NAMEPLATE) 208/230-60-1 208/230-60-1 208/230-60-1
ELECTRICAL AMPS 23.1 26.7 33.2
SPECIFICATION MIN CIRCUIT AMPACITY 28 32 40
MAX OVERCURRENT PROTECTION
(2)
45 50 60
COMPRESSOR TYPE SCROLL SCROLL SCROLL
RATED LOAD AMPS 17.9 19.9 26.4
LOCKED ROTOR AMPS 112 109 134
CONDENSER HORSEPOWER 1/4 1/4 1/4
FAN MOTOR RPM 1075 1075 1075
FULL LOAD AMPS 1.4 1.4 1.4
LOCKED ROTOR AMPS 2.9 2.9 2.9
CONDENSER FAN BLADE DIAMETER (INCHES) / # OF BLADES 22 / 4 22 / 4 22 / 4
CONDENSER FACE AREA (SQ. FT.) 17 17 19.1
COIL NUMBER OF ROWS 1 2 2
FINS PER INCH 24 16 16
EVAPORATOR HORSEPOWER - NO. OF SPEEDS 1/2 - 5 3/4 - 5 3/4 -5
BLOWER FULL LOAD AMPS 3.8 5.4 5.4
MOTOR LOCKED ROTOR AMPS NA NA NA
MOTOR SPEED TAP - COOLING
T2 T2 T2
RPM 1,050 1,050 1,050
EVAPORATOR
DIAMETER X WIDTH (INCHES) 10 X 8 10 X 8 11 X 8
BLOWER
RATED SCFM COOLING 1,300 1,600 1,600
HI EFFICIENCY COOLING CFM 1,300 1,600 1,600
5 TON NOMINAL COOLING CFM NA NA 1,800
FAN ONLY COOLING CFM 1,200 1,400 1,600
MAX EXTERNAL STATIC PRESS ("w.c.) 0.8 / 0.5** 0.8 / 0.5** 0.8 / 0.5**
EVAPORATOR FACE AREA (SQ. FT.) 6.2 6.2 7.0
COIL NUMBER OF ROWS 4 4 4
ALUMINUM FINS PER INCH 14 14 14
GENERAL FILTER SIZE (SQ. FT.)
(2) 20 x 20 x 1 (2) 20 x 20 x 1 (2) 20 x 25 x 1
INFORMATION DRAIN SIZE (INCHES) 3/4" 3/4" 3/4"
EXPANSION DEVICE (INDOOR / OUTDOOR) ORIFICE (0.074 / 0.065) ORIFICE (0.074 / 0.065) ORIFICE (0.086 / 0.071)
REFRIGERANT CHARGE R-410A (OZS.) 132 170 175
POWER SUPPLY CONDUIT KNOCKOUT SIZE (INCHES) 3/4, 1, 1-1/4 3/4, 1, 1-1/4 3/4, 1, 1-1/4
LOW VOLTAGE CONDUIT KNOCKOUT SIZE (INCHES) 1/2 1/2 1/2
LO PRESSURE SWITCH
OPENS / CLOSES PSIG 22 / 50 22 / 50 22 / 50
HI PRESSURE SWITCH - OPENS PSIG
OPENS / CLOSES PSIG 660 / 420 660 / 420 660 / 420
SHIPPING WEIGHT (LBS.) 385 410 415
OPERATING WEIGHT (LBS.) 375 400 405
(2)
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
*
Calculated external filter size based on air velocity of 300 ft/min.
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Unit specifications are subject to change without notice.
ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.
*PH14[42-60]H41E*
** When using a 20kW electric heater, unit is rated for 0.5 E.S.P. For all other electric heat sizes as well as units with no heater installed, the max E.S.P is 0.8.