GPH14H Technical Manual

22
COOLING PERFORMANCE DATA *PH1424H41**
MODEL: *PH1424H41**
EXPANDED PERFORMANCE DATA
COOLING OPERATION
Design Subcooling, 10 ± 2 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 9 ± 2°F @ the compressor suction access fitting connection.
Outdoor Ambient Temperature
65 75 85 95 105 115
Entering Indoor Wet Bulb Temperature
IDB*Airflow 596367715963677159636771596367715963677159636771
MBh 24.7 25.3 27.0 28.9 24.2 24.7 26.4 28.2 23.6 24.1 25.8 27.5 23.0 23.5 25.1 26.9 21.9 22.3 23.9 25.5 20.3 20.7 22.1 23.6
S/T 0.93 0.87 0.71 0.53 0.96 0.90 0.74 0.55 1.00 0.93 0.76 0.56 1.00 0.96 0.78 0.58 1.00 1.00 0.81 0.60 1.00 1.00 0.82 0.61
Delta T222118152222191523221915222219152122191519201714
955 KW 1.56 1.60 1.65 1.71 1.69 1.73 1.78 1.84 1.80 1.84 1.90 1.97 1.90 1.94 2.01 2.08 1.98 2.03 2.10 2.17 2.05 2.10 2.17 2.25
AMPS 6.5 6.6 6.8 7.1 7.0 7.1 7.3 7.6 7.5 7.7 7.9 8.2 8.0 8.2 8.4 8.7 8.5 8.7 9.0 9.3 9.0 9.2 9.5 9.8
HI PR 240 259 273 285 270 290 306 320 307 330 349 363 349 376 397 414 393 423 447 466 434 467 493 515
LO PR 113 120 131 140 119 127 139 148 124 132 144 154 130 139 152 161 137 145 159 169 141 150 164 175
MBh 24.0 24.6 26.2 28.0 23.5 24.0 25.6 27.4 22.9 23.4 25.0 26.7 22.4 22.8
24.4
26.1 21.2 21.7 23.2 24.8 19.7 20.1 21.5 23.0
S/T 0.89 0.83 0.68 0.51 0.92 0.86 0.70 0.53 0.94 0.89 0.72 0.54 0.97 0.91
0.74
0.56 1.00 0.95 0.77 0.58 1.00 0.96 0.78 0.58
Delta T2322191523221916232219162423
20
16 23 22 19 15 21 21 18 14
80 850 KW 1.55 1.58 1.64 1.69 1.67 1.71 1.77 1.83 1.78 1.82 1.89 1.95 1.88 1.92
1.99
2.06 1.96 2.01 2.08 2.15 2.03 2.08 2.15 2.23
AMPS 6.4 6.6 6.8 7.0 6.9 7.1 7.3 7.5 7.5 7.6 7.9 8.1 7.9 8.1
8.4
8.78.48.68.99.28.99.19.49.7
HI PR 238 256 270 282 267 287 303 316 304 327 345 360 346 372
393
410 389 419 442 461 430 463 488 510
LO PR 112 119 130 139 118 126 137 146 123 131 143 152 129 137
150
160 135 144 157 167 140 149 163 173
MBh 22.2 22.7 24.2 25.9 21.7 22.1 23.6 25.3 21.1 21.6 23.1 24.7 20.6 21.1 22.5 24.1 19.6 20.0 21.4 22.9 18.2 18.6 19.8 21.2
S/T 0.86 0.80 0.65 0.49 0.89 0.83 0.68 0.51 0.91 0.85 0.69 0.52 0.94 0.88 0.72 0.54 0.97 0.91 0.74 0.56 0.98 0.92 0.75 0.56
Delta T232220162423201624232016242320162423201622211815
745 KW 1.51 1.54 1.60 1.65 1.63 1.67 1.72 1.78 1.74 1.78 1.84 1.90 1.83 1.87 1.94 2.00 1.91 1.96 2.02 2.09 1.98 2.03 2.10 2.17
AMPS 6.3 6.4 6.6 6.8 6.7 6.9 7.1 7.3 7.3 7.4 7.7 7.9 7.7 7.9 8.2 8.4 8.2 8.4 8.6 9.0 8.7 8.9 9.1 9.5
HI PR 231 248 262 274 259 279 294 307 295 317 335 349 335 361 381 398 377 406 429 447 417 449 474 494
LO PR 109 116 126 134 115 122 133 142 119 127 139 148 125 133 146 155 131 140 152 162 136 144 158 168
NOTE: Shaded area ref lects A RI rating conditions
MBh 25.2 25.7 26.9 28.7 24.6 25.1 26.3 28.0 24.0 24.5 25.6 27.3 23.4 23.9 25.0 26.7 22.3 22.7 23.8 25.3 20.6 21.0 22.0 23.5
S/T 0.98 0.94 0.85 0.69 1.00 0.98 0.88 0.71 1.00 1.00 0.90 0.73 1.00 1.00 0.93 0.76 1.00 1.00 0.97 0.79 1.00 1.00 0.98 0.79
Delta T242322192424221923242219232322192122221920202118
955 KW 1.58 1.61 1.66 1.72 1.70 1.74 1.80 1.86 1.81 1.86 1.92 1.98 1.91 1.96 2.02 2.09 2.00 2.04 2.11 2.19 2.07 2.12 2.19 2.27
AMPS 6.5 6.7 6.9 7.1 7.0 7.2 7.4 7.7 7.6 7.8 8.0 8.3 8.1 8.3 8.5 8.8 8.6 8.8 9.0 9.4 9.0 9.3 9.5 9.9
HI PR 243 261 276 288 272 293 309 323 310 333 352 367 353 380 401 418 397 427 451 470 439 472 498 520
LO PR 114 122 133 141 121 128 140 149 125 133 146 155 132 140 153 163 138 147 160 171 143 152 166 177
MBh 24.4 24.9 26.1 27.8 23.9 24.3 25.5 27.2 23.3 23.8 24.9 26.5 22.7 23.2 24.3 25.9 21.6 22.0 23.1 24.6 20.0 20.4 21.4 22.8
S/T 0.93 0.90 0.81 0.66 0.96 0.93 0.84 0.68 0.99 0.95 0.86 0.70 1.00 0.99 0.89 0.72 1.00 1.00 0.92 0.75 1.00 1.00 0.93 0.76
Delta T252423202525232025252320252523202324232022222219
85 850 KW 1.56 1.60 1.65 1.71 1.69 1.73 1.78 1.84 1.80 1.84 1.90 1.97 1.90 1.94 2.01 2.08 1.98 2.03 2.10 2.17 2.05 2.10 2.17 2.25
AMPS 6.5 6.6 6.8 7.1 7.0 7.1 7.3 7.6 7.5 7.7 7.9 8.2 8.0 8.2 8.4 8.7 8.5 8.7 9.0 9.3 9.0 9.2 9.5 9.8
HI PR 240 259 273 285 270 290 306 320 307 330 349 363 349 376 397 414 393 423 447 466 434 467 493 515
LO PR 113 120 131 140 119 127 139 148 124 132 144 154 130 139 152 161 137 145 159 169 141 150 164 175
MBh 22.6 23.0 24.1 25.7 22.0 22.5 23.5 25.1 21.5 21.9 23.0 24.5 21.0 21.4 22.4 23.9 19.9 20.3 21.3 22.7 18.5 18.8 19.7 21.0
S/T 0.90 0.87 0.78 0.63 0.93 0.90 0.81 0.66 0.95 0.92 0.83 0.67 0.98 0.95 0.86 0.70 1.00 0.99 0.89 0.72 1.00 0.99 0.90 0.73
Delta T252523202525242025252420262524212525232023232219
745 KW 1.52 1.56 1.61 1.66 1.65 1.68 1.74 1.80 1.75 1.79 1.85 1.92 1.85 1.89 1.95 2.02 1.93 1.97 2.04 2.11 2.00 2.04 2.11 2.19
AMPS 6.3 6.5 6.6 6.9 6.8 6.9 7.1 7.4 7.3 7.5 7.7 8.0 7.8 8.0 8.2 8.5 8.3 8.5 8.7 9.0 8.7 8.9 9.2 9.5
HI PR 233 251 265 276 262 281 297 310 297 320 338 353 339 365 385 402 381 410 433 452 421 453 479 499
LO PR 110 117 127 136 116 123 135 143 120 128 140 149 127 135 147 157 133 141 154 164 137 146 159 170
* Entering Indoor Dry Bulb Temperature NOTE: Shaded area is A HRI Rating Conditions KW = Total system pow er
High and low pressures are measured at the liquid and suction acc ess fittings. AMPS: Unit amps (c omp.+ ev aporator + condenser f an motors)