GPH14H Technical Manual

PACKAGE HEAT PUMP SPECIFICATIONS
33
EXPANDED PERFORMANCE DATA
MODEL: *PH1424H41** HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 -5 -10
MBh 28.7 27.1 25.5 23.9 22.8 22.1 20.5 18.9 16.2 15.0 13.8 13.0 12.5 11.2 10.0 8.7 7.4 6.1
DELTA T 31.2 29.6 27.8 26.0 24.8 24.1 22.4 20.6 17.6 16.3 15.0 14.2 13.6 12.2 10.8 9.5 8.1 6.6
KW 1.86 1.82 1.78 1.75 1.73 1.71 1.67 1.63 1.65 1.61 1.58 1.55 1.54 1.50 1.46 1.42 1.38 1.34
AMPS9.18.47.97.57.27.16.76.46.25.95.65.55.55.24.94.64.33.9
COP 4.51 4.36 4.19 4.00 3.87 3.78 3.59 3.39 2.87 2.71 2.56 2.45 2.38 2.19 2.00 1.79 1.57 1.32
EER 15.4 14.9 14.3 13.7 13.2 12.9 12.3 11.6 9.8 9.3 8.7 8.4 8.1 7.5 6.8 6.1 5.4 4.5
HI PR 367 352 338 324 316 310 298 286 274 262 251 245 241 232 223 214 206 199
LO PR 142 132 123 113 107 103 95 84 76 68 60 56 54 45 39 33 29 23
Above inf ormation is f or nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
MODEL: *PH1430H41** HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 34.7 32.8 30.9 28.9 27.6 26.7 24.8 22.9 19.2 17.7 16.3 15.4 14.8 13.3 11.8 10.3 8.8 7.2
DELTA T 30.6 29.0 27.3 25.5 24.3 23.6 21.9 20.2 16.9 15.6 14.4 13.6 13.1 11.7 10.4 9.1 7.7 6.3
KW 2.26 2.22 2.17 2.13 2.10 2.08 2.04 1.99 1.98 1.93 1.89 1.86 1.84 1.79 1.75 1.70 1.66 1.61
AMPS11.010.39.79.18.88.78.27.87.57.26.96.86.76.46.05.75.34.9
COP 4.48 4.33 4.16 3.97 3.84 3.76 3.56 3.36 2.84 2.68 2.53 2.42 2.36 2.17 1.97 1.77 1.55 1.30
EER 15.3 14.8 14.2 13.6 13.1 12.8 12.2 11.5 9.7 9.2 8.6 8.3 8.1 7.4 6.7 6.0 5.3 4.5
HI PR 374 359 345 330 322 316 304 291 279 267 256 250 245 236 227 218 210 203
LO PR13412411710710197898072645652514337312721
Above inf ormation is f or nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
MODEL: *PH1436H41** HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 41.5 39.3 37.0 34.6 33.0 32.0 29.7 27.4 26.9 24.8 22.9 21.6 20.8 18.7 16.5 14.4 12.3 10.1
DELTA T 32.0 30.3 28.5 26.7 25.5 24.7 22.9 21.1 20.8 19.2 17.7 16.7 16.1 14.4 12.8 11.1 9.5 7.8
KW 2.74 2.68 2.63 2.57 2.54 2.52 2.47 2.41 2.64 2.58 2.52 2.48 2.46 2.39 2.33 2.27 2.21 2.15
AMPS 13.5 12.6 11.9 11.2 10.9 10.7 10.1 9.7 9.3 8.9 8.5 8.4 8.3 7.9 7.4 7.1 6.6 6.1
COP 4.44 4.29 4.12 3.93 3.80 3.71 3.52 3.32 2.98 2.82 2.66 2.55 2.48 2.28 2.08 1.86 1.63 1.37
EER 15.2 14.6 14.1 13.4 13.0 12.7 12.0 11.4 10.2 9.6 9.1 8.7 8.5 7.8 7.1 6.4 5.6 4.7
HI PR 367 352 338 323 316 310 298 286 274 262 251 245 241 232 223 214 206 199
LO PR13512511710810298908072655753514337312721
Above inf ormation is f or nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
*PH14[24-36]H41**
PERFORMANCE TEST
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:
If conditions vary from this, results will change as follows:
1. As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low
and high side pressures and power will not change.
2. As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will
occur in low and high side pressures and power.
A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.
A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.
A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.
A properly operating unit should be within plus or minus 3 Amps of the typical value shown.