GPH14H Technical Manual
PACKAGE HEAT PUMP SPECIFICATIONS
34
EXPANDED PERFORMANCE DATA
MODEL: *PH1442H41** HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 47.144.642.039.337.536.333.831.126.724.622.721.420.618.516.414.312.210.0
DELTA T33.631.829.928.026.725.924.022.219.017.516.115.214.713.211.710.2 8.7 7.1
KW 3.07 3.01 2.95 2.89 2.85 2.83 2.77 2.71 2.39 2.33 2.28 2.25 2.23 2.18 2.12 2.07 2.02 1.97
AMPS 12.5 11.6 10.9 10.3 9.9 9.8 9.2 8.8 8.4 8.1 7.7 7.5 7.5 7.1 6.7 6.3 5.9 5.3
COP 4.50 4.34 4.17 3.98 3.85 3.76 3.57 3.36 3.27 3.09 2.91 2.78 2.71 2.49 2.26 2.02 1.77 1.49
EER 15.4 14.8 14.2 13.6 13.1 12.9 12.2 11.5 11.2 10.5 9.9 9.5 9.2 8.5 7.7 6.9 6.0 5.1
HI PR 370 355 341 326 319 313 301 288 276 264 253 247 243 234 225 215 208 200
LO PR13712711910910399918173655854524438322822
Above inf ormation is f or nominal CFM and 70 degree indoor dry bulb. Instantaneous c apacity listed.
MODEL: *PH1448H41** HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 56.653.650.447.145.043.640.537.432.429.927.526.025.022.519.917.414.812.1
DELTA T32.731.029.227.326.025.223.421.618.717.315.915.014.513.011.510.1 8.6 7.0
KW 3.61 3.54 3.47 3.40 3.36 3.33 3.26 3.19 3.17 3.10 3.03 2.99 2.96 2.89 2.82 2.75 2.67 2.60
AMPS 18.5 17.2 16.2 15.4 14.9 14.6 13.8 13.2 12.7 12.2 11.7 11.5 11.3 10.8 10.2 9.7 9.1 8.3
COP 4.59 4.43 4.25 4.06 3.92 3.84 3.64 3.43 2.99 2.82 2.66 2.55 2.48 2.28 2.07 1.85 1.62 1.37
EER 15.7 15.1 14.5 13.9 13.4 13.1 12.4 11.7 10.2 9.6 9.1 8.7 8.5 7.8 7.1 6.3 5.5 4.7
HI PR 383 368 353 338 330 324 311 299 286 273 262 256 251 242 233 223 215 208
LO PR13512611810810298908073655753514337312722
Above inf ormation is f or nominal CFM and 70 degree indoor dry bulb. Instantaneous c apacity listed.
MODEL: *PH1460H41** HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 68.564.961.057.154.552.849.145.242.138.935.833.832.529.225.922.619.315.8
DELTA T39.637.535.333.031.530.628.426.224.422.520.719.618.816.915.013.111.1 9.1
KW 4.76 4.67 4.57 4.47 4.41 4.37 4.28 4.18 4.08 3.98 3.88 3.83 3.79 3.69 3.59 3.50 3.40 3.30
AMPS 23.9 22.2 20.9 19.7 19.0 18.7 17.7 16.8 16.1 15.4 14.8 14.4 14.2 13.6 12.7 12.0 11.2 10.2
COP 4.21 4.07 3.91 3.74 3.61 3.54 3.36 3.17 3.02 2.86 2.70 2.58 2.51 2.32 2.11 1.89 1.66 1.40
EER 14.4 13.9 13.4 12.8 12.3 12.1 11.5 10.8 10.3 9.8 9.2 8.8 8.6 7.9 7.2 6.5 5.7 4.8
HI PR 407 390 375 358 350 343 330 317 303 290 278 272 267 257 247 237 228 220
LO PR 130 121 113 104 98 94 87 77 70 62 55 51 49 41 36 30 26 21
Above inf ormation is f or nominal CFM and 70 degree indoor dry bulb. Instantaneous c apacity listed.
*PH14[42-60]H41**
PERFORMANCE TEST
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:
If conditions vary from this, results will change as follows:
1. As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low
and high side pressures and power will not change.
2. As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will
occur in low and high side pressures and power.
A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.
A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.
A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.
A properly operating unit should be within plus or minus 3 Amps of the typical value shown.