GPH14H Technical Manual

PACKAGE HEAT PUMP SPECIFICATIONS
8
GPH14[24-36]H41A*
(2)
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
*
Calculated external filter size based on air velocity of 300 ft/min.
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.
GPH1424H41** GPH1430H41** GPH1436H41**
COOLING
COOLING CAPACITY, BTUH 24,000 28,400 36,000
CAPACITY
SEER / EER 14.5 / 12.0 14.0 / 12.0 14.0 / 12.0
HEATING
47°/43°F 22,800 27,600 32,200
RATING
35°/33°F 15,500 18,600 26,000
17°/15°F 13,000 15,400 21,400
HSPF 8.0 8.0 8.0
UNIT
VOLTAGE (NAMEPLATE) 208/230-60-1 208/230-60-1 208/230-60-1
ELECTRICAL
AMPS 15.4 17.1 20.1
SPECIFICATION
MIN CIRCUIT AMPACITY 12.5 15.6 24.2
MAX OVERCURRENT PROTECTION
(2 )
20 25 40
COMPRESSOR
TYPE SCROLL SCROLL SCROLL
RATED LOAD AMPS 12.8 14.1 16.7
LOCKED ROTOR AMPS 58.3 73 79
CONDENSER
HORS EPOW ER 1/6 1/6 1/ 4
FAN MOTOR
RPM 815 815 1075
FULL LOAD AMPS 1.1 1.1 1.5
LOCKED ROTOR AMPS 1.7 1.7 3.0
CONDENSER FAN
BLADE DIAMETER (INCHES) / # OF BLADES 22 / 3 22 / 3 22 / 4
CONDENSER
FACE AREA (SQ. FT.) 13.4 13.4 17
COIL
NUMBER OF ROWS 1 1 1
FINS PER INCH 24 24 24
EVAPORATOR
HORS EPOW ER - N O. OF SPEEDS 1/ 2 - 5 1/2 - 5 1/ 2 - 5
BLOWER
FULL LOAD AMPS 1.50 1.86 1.86
MOTOR
LOCKED ROTOR AMPS NA NA NA
MOTOR SPEED TAP - COOLING T2 T2 T2
RPM 1,050 1,050 1,050
EVAPORATOR
DIAMETER X WIDTH (INCHES) 10 X 8 10 X 8 10 X 8
BLOWER
RATED SCFM COOLING 850 1,050 1,200
HI EFFICIENCY COOLING CFM 850 1,050 1,200
FAN ONLY COOLING CFM 800 950 1,100
MAX EXTERNAL STATIC PRESS ("w.c.) 0.5 0.5 0.5
EVAPORATOR
FACE AREA (SQ. FT.) 5.25 4.67 5.20
COIL
NUMBER OF ROWS 3 4 3
FINS PER INCH 16 16 14
GENERAL
FILTER SIZE (SQ. FT.) 20 x 20 x 1 20 x 25 x 1 25 x 25 x 1
INFORMATION
DRAIN SIZE (INCHES) 3/4" 3/4" 3/4"
EXPANSION DEVICE (INDOOR / OUTDOOR) ORIFICE (0.057 / 0.049) ORIFICE (0.065 / 0.047) ORIFICE (0.068 / 0.067)
REFRIGERANT CHARGE R-410A (OZS.) 85 105 125
POWER SUPPLY CONDUIT KNOCKOUT SIZE (") 3/4, 1, 1-1/4 3/4, 1, 1-1/4 3/4, 1, 1-1/4
LOW VOLTAGE CONDUIT KNOCKOUT SIZE (") 1/2 1/2 1/2
LO PRES SURE SWITCH
OPENS / CLOSES PSIG 22 / 50 22 / 50 22 / 50
HI PRESSURE SWITCH - OPENS PSIG
OPENS / CLOSES PSIG 660 / 420 660 / 420 660 / 420
SHIPPING WEIGHT (LBS.) 325 325 385
OPERATING WEIGHT (LBS.) 315 315 375