Specifications

Product SPecificationS
Product SPecificationS
SS-GPH14H www.goodmanmfg.com 19
airflow Data
Model Speed* Volts
E.S.P. (In. of H
2
O)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80
GPH14
24H41A*
T1 230
CFM 934 759 755 638 581 489 - -
Was 95 77 76 73 83 90 - -
T2,T3 230
CFM 990 837 801 744 696 652 601 -
Was 107 94 105 110 119 133 142 -
T4, T5 230
CFM 1,061 989 947 925 876 - - -
Was 126 134 146 158 169 - - -
GPH14
24H41C*
T1 230
CFM 914 866 818 770 722 674 626 578
Was 69 80 91 102 114 125 136 147
T2,T3 230
CFM 914 866 818 770 722 674 626 578
Was 69 80 91 102 114 125 136 147
T4, T5 230
CFM 1,064 1,016 968 920 872 824 776 728
Was 97 108 120 131
142 153 165 176
GPH14
30H41A*
T1 230
CFM 1,022 929 894 829 797 748 695 643
Was 116 114 126 134 144 156 168 173
T2,T3 230
CFM 1,103 1,063 1,012 962 937 - - -
Was 142 154 165 173 185 - - -
T4, T5 230
CFM 1,285 1,240 1,202 1,163 1,124 1,076 1,046 1,003
Was 205 218 231 244 257 268 280 288
GPH14
30H41C*
T1 230
CFM 1,005 961 918 874 831 787 744 700
Was 91 102 114 125 137 149 160 172
T2,T3 230
CFM 1,110 1,067 1,023 980 936 893 849 806
Was 120 132 144 155 167 178 190 202
T4, T5 230
CFM 1,287 1,244 1,200 1,157 1,113 1,070 1,026 983
Was 170 182 194 205 217 228 240 252
GPH14
36H41A*
T1 230
CFM 1,234
1,111 1,071 1,024 933 922 - -
Was 144 140 152 164 179 183 - -
T2,T3 230
CFM 1,287 1,232 1,186 1,133 1,099 1,053 - -
Was 162 175 187 201 213 221 - -
T4, T5 230
CFM 1,381 1,325 1,277 1,233 1,181 1,144 - -
Was 195 203 217 233 247 258 - -
GPH14
36H41C*
T1 230
CFM 1,151 1,097 1,042 988 933 879 824 770
Was 132 144 156 169 181 194 206 219
T2,T3 230
CFM 1,261 1,215 1,169 1,123 1,076 1,030 984 937
Was 131 144 157 169 182 194 207 220
T4, T5 230
CFM 1,376 1,330 1,284 1,237 1,191 1,145 1,099 1,052
Was 170 182 195 207 220 233 245 258
* Speed set at T2 at factory.