Specifications
Table Of Contents
Product SPecificationS
Product SPecificationS
SS-GPH14H www.goodmanmfg.com 19
airflow Data
Model Speed* Volts
E.S.P. (In. of H
2
O)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80
GPH14
24H41A*
T1 230
CFM 934 759 755 638 581 489 - -
Was 95 77 76 73 83 90 - -
T2,T3 230
CFM 990 837 801 744 696 652 601 -
Was 107 94 105 110 119 133 142 -
T4, T5 230
CFM 1,061 989 947 925 876 - - -
Was 126 134 146 158 169 - - -
GPH14
24H41C*
T1 230
CFM 914 866 818 770 722 674 626 578
Was 69 80 91 102 114 125 136 147
T2,T3 230
CFM 914 866 818 770 722 674 626 578
Was 69 80 91 102 114 125 136 147
T4, T5 230
CFM 1,064 1,016 968 920 872 824 776 728
Was 97 108 120 131
142 153 165 176
GPH14
30H41A*
T1 230
CFM 1,022 929 894 829 797 748 695 643
Was 116 114 126 134 144 156 168 173
T2,T3 230
CFM 1,103 1,063 1,012 962 937 - - -
Was 142 154 165 173 185 - - -
T4, T5 230
CFM 1,285 1,240 1,202 1,163 1,124 1,076 1,046 1,003
Was 205 218 231 244 257 268 280 288
GPH14
30H41C*
T1 230
CFM 1,005 961 918 874 831 787 744 700
Was 91 102 114 125 137 149 160 172
T2,T3 230
CFM 1,110 1,067 1,023 980 936 893 849 806
Was 120 132 144 155 167 178 190 202
T4, T5 230
CFM 1,287 1,244 1,200 1,157 1,113 1,070 1,026 983
Was 170 182 194 205 217 228 240 252
GPH14
36H41A*
T1 230
CFM 1,234
1,111 1,071 1,024 933 922 - -
Was 144 140 152 164 179 183 - -
T2,T3 230
CFM 1,287 1,232 1,186 1,133 1,099 1,053 - -
Was 162 175 187 201 213 221 - -
T4, T5 230
CFM 1,381 1,325 1,277 1,233 1,181 1,144 - -
Was 195 203 217 233 247 258 - -
GPH14
36H41C*
T1 230
CFM 1,151 1,097 1,042 988 933 879 824 770
Was 132 144 156 169 181 194 206 219
T2,T3 230
CFM 1,261 1,215 1,169 1,123 1,076 1,030 984 937
Was 131 144 157 169 182 194 207 220
T4, T5 230
CFM 1,376 1,330 1,284 1,237 1,191 1,145 1,099 1,052
Was 170 182 195 207 220 233 245 258
* Speed set at T2 at factory.