Product SPecificationS
Product SPecificationS
SS-GPH14H www.goodmanmfg.com 3
SpecificationS
GPH14
24H41A*
GPH14
24H41C*
GPH14
30H41A*
GPH14
30H41C*
GPH14
36H41A*
GPH14
36H41C*
AHRI Cooling Capacity (BTU/h) 24,000 24,000 28,400 28,400 36,000 36,000
Sensible BTU/h 18,200 18,200 23,400 23,400 27,400 27,400
SEER / EER 14.5 / 12.0 14.5 / 12.0 14.0 / 12.0 14.0 / 12.0 14.0 / 11.5 14.0 / 11.5
Decibels 76 76 76 76 78 78
AHRI Numbers 4385132 5677874 4385133 5677875 4385134 5677876
BTU/h (47°F) 22,800 22,800 27,600 27,600 32,200 32,200
C.O.P. (47°F) 3.8 3.8 3.8 3.8 3.7 3.7
BTU/h (17°F) 13,000 13,000 15,400 15,400 20,400 20,400
C.O.P. (17°F) 2.4 2.4 2.5 2.5 2.4 2.4
HSPF 8.0 8.0 8.0 8.0 8.0 8.0
Type EEM EEM EEM EEM EEM EEM
Wheel (D x W) 10 x 8 10 x 8 10 x 8 10 x 8 10 x 8 10 x 8
Cooling CFM 875 875 1,050 1,050 1,200 1,200
Fan-Only CFM 800 800 950 950 1,100 1,100
RLA 1.5 1.5 1.86 1.86 1.86 1.86
No. of Speeds 5 5 5 5 5 5
Horsepower - RPM ½ - 1,050 ½ - 1,050 ½ - 1,050 ½ - 1,050 ½ - 1,050 ½ - 1,050
Face Area (
2
) 5.25 5.2 4.67 5.2 5.2 6.2
Rows Deep/ Fins per Inch 3/ 16 3/ 14 4/ 16 3/ 14 3/ 14 3/ 14
Indoor Metering Device Size 0.057 0.061 0.065 0.065 0.068 0.068
Filter Size (
2
) 20 x 20 x 1 20 x 20 x 1 20 x 25 x 1 20 x 25 x 1 25 x 25 x 1 25 x 25 x 1
Drain Size (NPT) ¾" ¾" ¾" ¾" ¾" ¾"
Refrigerant Charge (oz.) 85 105 105 105 125 125
Horsepower - RPM 1/6 - 815 1/6 - 815 1/6 - 815 1/6 - 815 ¼ - 1075 ¼ - 1075
RLA/LRA 1.1 / 1.7 1.1 / 1.7 1.1 / 1.7 1.1 / 1.7 1.5 /3.0 1.5 /3.0
Fan Diameter / # Fan Blades 22 / 3 22 / 3 22 / 3 22 / 3 22 / 4 22 / 4
Face Area (
2
) 13.4 13.4 13.4 13.4 17 17
Outdoor Metering Device Size 0.049 0.047 0.047 0.047 0.067 0.063
Rows Deep/ Fins per Inch 1 / 24 1 / 24 1 / 24 1 / 24 1 / 24 1 / 24
Quanty / Type 1 / Scroll / Single 1 / Scroll / Single 1 / Scroll / Single 1 / Scroll / Single 1 / Scroll / Single 1 / Scroll / Single
Compressor RLA/LRA 12.8 / 58.3 12.8 / 58.3 14.1 / 73 14.1 / 73 16.7 / 79 16.7 / 79
Voltage/Phase/ Frequency 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60
Indoor Blower FLA 1.5 1.5 1.86 1.86 1.86 1.86
Outdoor Fan RLA 1.1 1.1 1.1 1.1 1.4 1.4
Total Unit Amps 15.4 15.4 17.06 17.06
19.96 19.96
Min. Circuit Ampacity¹ 18.6 18.6 20.6 20.6 24.2 24.2
Min. Overcurrent Protecon (amps)² 30 30 30 30 40 40
315 / 325 315 / 325 315 / 325 315 / 325 375 / 385 375 / 385
¹ Wire size should be determined in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
² Must use me-delay fuses or HACR-type circuit breakers of the same size as noted.
Always check the S&R plate for electrical data on the unit being installed.