GPH16H Submittal

2 www.goodmanmfg.com SS-GPH16H
SS-GPH16H www.goodmanmfg.com 3
Product Specifications
GPH16
24H41A*
GPH16
30H41A*
GPH16
36H41A*
GPH16
42H41A*
GPH16
48H41A*
GPH16
60H41A*
Cooling Capacity
AHRI Cooling Capacity (BTU/h) 24,000 28,400 36,000 40,500 46,000 57,500
Sensible BTU/h 18,200 23,400 27,400 29,600 35,400 40,500
SEER / EER 16.0 / 13.0 16.0 / 12.5 16.0 / 13.0 16.0 / 12.0 16.0 / 12.0 15.5/12
Decibels 76 76 78 78 80 80
AHRI Numbers 7953308 7953310 7953311 7953312 7953729
9008583
Heating Capacity
BTU/h (47°F) 22,800 27,600 32,200 37,600 44,000 54,500
C.O.P. (47°F) 3.8 3.8 3.8 3.8 3.8 3.6
BTU/h (17°F) 13,000 15,400 20,400 21,600 26,000 33,800
C.O.P. (17°F) 2.4 2.5 2.4 2.4 2.4 2.4
HSPF 8.0 8.0 8.0 8.0 8.0
8.2
Evaporator Motor
Type EEM EEM EEM EEM EEM EEM
Wheel (D x W) 10 x 8 10 x 8 10 x 8 10 x 8 10 x 8 11X8
Cooling CFM 875 1,050 1,200 1,300 1,600 1,700
Fan-Only CFM 800 950 1,100 1,200 1,400 1,600
RLA 3.8 3.8 3.8 3.8 5.4 5.4
No. of Speeds 5 5 5 5 5 5
Horsepower - RPM ½ - 1,050 ½ - 1,050 ½ - 1,050 ½ - 1,050 ¾ - 1,050
¾ - 1,050
Evaporator Coil
Face Area (
2
) 5.2 5.2 6.2 6.2 6.2 7
Rows Deep/ Fins per Inch 3/ 14 3/ 14 4/ 14 4/ 14 4/ 14 4/ 14
Indoor Metering Device Size TXV TXV TXV TXV TXV TXV
Filter Size (
2
) 20 x 20 x 1 20 x 25 x 1 25 x 25 x 1 (2) 20x20x1 (2) 20x20x1 (2) 20x25x1
Drain Size (NPT) ¾" ¾" ¾" ¾" ¾" ¾"
Refrigerant Charge (oz.) 116 116 170 170 170
175
Condenser Fan / Coil
Horsepower - RPM 1/6 - 815 1/6 - 815 ¼ - 1075 ¼ - 1075 ¼ - 1075 ¼ - 1075
RLA/LRA 1.1 / 1.7 1.1 / 1.7 1.5 /3.0 1.4 / 2.9 1.4 / 2.9 1.4 / 2.9
Fan Diameter / # Fan Blades 22 / 3 22 / 3 22 / 4 22 / 4 22 / 4 22 / 4
Face Area (
2
) 14.3 14.3 17 17 17 19
Outdoor Metering Device Size 0.047 0.047 0.057 0.059 TXV TXV
Rows Deep/ Fins per Inch 2 / 16 2 / 16 2 / 16 2 / 16 2 / 16
2 / 20
Compressor
Quanty / Type / Stage 1 / Scroll / Single 1 / Scroll / Single 1 / Scroll / Single 1 / Scroll / Single 1 / Scroll / Two 1 / Scroll / two
Compressor RLA/LRA 12.8 / 58.3 14.1 / 73 16.7 / 79 17.9 / 112 21.2 / 104
26.4/ 134
Electrical Data
Voltage/ Phase (60 Hz) 208-230/ 1 208-230/ 1 208-230/ 1 208-230/ 1 208-230/ 1 208-230/ 1
Indoor Blower FLA 3.8 3.8 3.8 3.8 5.4 5.4
Outdoor Fan RLA 1.1 1.1 1.4 1.4 1.4 1.4
Total Unit Amps 17.7 19 21.9 23.1 28 33.2
Min. Circuit Ampacity¹ 21 23 27 28 35 40
Min. Overcurrent Protecon ² 30 amps 35 amps 40 amps 45 amps 50 amps
60 amps
Operating Weights (lbs) 315 315 375 375 400
405
Shipping Weights (lbs) 325 325 385 385 410
415
¹ Wire size should be determined in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
² Must use me-delay fuses or HACR-type circuit breakers of the same size as noted.
Always check the S&R plate for electrical data on the unit being installed.