Product Specifications
GPH16
24M41A*
GPH16
30M41A*
GPH16
36M41A*
GPH16
42M41A*
GPH16
48M41C*
GPH16
60M41A*
Cooling Capacity
Total BTU/h 24,000 29,000 33,600 41,000 47,000
58,000
Sensible BTU/h 18,200 22,000 25,200 30,000 35,800
44,000
SEER / EER 16.0/ 12.5 15.5/ 12.0 16.0/ 12.0 16.0/ 12.0 16.0/ 12.0
16.0/ 12.0
Decibels 76 76 76 78 78
78
AHRI #s 8143312 8143313 8143314 8143315 8143316 9134480
Heating Capacity
BTU/h (47°F) 22,800 28,400 33,600 38,000 45,500
55,000
C.O.P (47°F) 3.6 3.5 3.6 3.6 3.7
3.8
BTU/h (17°F) 12,500 16,600 19,400 21,600 27,000
30,000
C.O.P (17°F) 2.3 2.4 2.4 2.3 2.4
2.4
HSPF 8.0 8.0 8.2 8.2 8.2
8.2
Evaporator Motor
Type ECM ECM ECM ECM ECM
ECM
Wheel (D x W) 10 x 9 10 x 9 10 x 9 10 x 9 10 x 9
11x 10
Nominal Cooling CFM 850 1,050 1,200 1,300 1,600
2,000
FLA 4.3 4.3 4.3 5.8 5.8
6.9
No. of Speeds Variable Variable Variable Variable Variable
5
Horsepower - RPM ½ -1,050 ½ -1,050 ½ -1,050 ¾ - 1,050 ¾ - 1,050
1 - 1,050
Evaporator Coil
Face Area (²) 4.5 4.5 4.5 6.2 6.2
8.9
Rows Deep/ Fin per Inch 4/ 14 4/ 14 4/ 14 4/ 14 4/ 14
4/ 16
Expansion Device TXV TXV TXV TXV TXV
TXV
Drain Size (NPT) ¾” ¾” ¾” ¾” ¾”
¾"
R-410A Refrigerant Charge (oz.) 137 137 137 170 170
240
Condenser Fan / Coil
Horsepower - RPM ¼ - 850 ¼ - 850 ¼ - 850 ¼ - 1,075 ¼ - 1,075
1/3 - 1,090
FLA/LRA 1.5/ 3.0 1.5/ 3.0 1.5/ 3.0 1.4 / 2.9 1.4 / 2.9
2/ 4.4
Fan Diameter / # Fan Blades 22 / 3 22 / 3 22 / 3 22 / 3 22 / 3
22 / 4
Expansion Device TXV TXV TXV TXV TXV
TXV
Face Area (²) 15.5 15.5 15.5 19.4 19.4
19
Rows Deep/ Fin per Inch 2 / 16 2 / 16 2 / 16 2 / 16 2 / 16
2 / 20
Compressor
Quanty 1 1 1 1 1
1
Type Scroll Scroll Scroll Scroll Scroll
Scroll
Stage Two Two Two Two Two
Two
Electrical Data
Voltage/ Phase/ Hz 208-230/ 1 208-230/ 1 208-230/ 1 208-230/ 1 208-230/ 1
208-230/ 1
Compressor RLA/ LRA 11.7 / 58.3 13.1 / 73 15.3 / 83 17.9 / 96 21.2 / 104
26.9/ 152.9
Indoor Blower FLA 4.3 4.3 4.3 5.8 5.8
6.9
Total Unit Amps 17.5 18.9 21.1 25.1 28.4
35.8
Min. Circuit Ampacity¹ 20.4 22.2 24.9 29.6 33.7
42.5
Max. Overcurrent Protecon² 30 35 40 45 50
60
Shipping Weight (lbs) 366 375 428 472 470
620
ENERGY STAR® Certified NO NO NO NO NO
¹
Wire size should be determined in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
²
May use fuses or HACR-type circuit breakers of the same size as noted.