Installation Manual

32
external static pressure. The supply duct pressure must be
read between the furnace and the cooling coil. This read-

plate from the end on the coil; drilling a test hole in it and

at the test hole. Tape up the test hole after your test is
complete. The negative pressure must be read between the


air that can cause excessive temperature rise. This can
cause limit switch tripping and heat exchanger failure.
To determine total external duct static pressure, proceed
as follows;
 -



 

 
Example:
-1
0
1 2
3
Difference is 4
static reading from return duct = -.1” w.c.
static reading from supply duct = .3” w.c.
total external static pressure on this system = .4” w.c.
Both readings may be taken simultaneously and read
directly on the manometer if so desired. If an air conditioner
coil or Electronic Air Cleaner is used in conjunction with the
furnace, the readings must also include theses components,
as shown in the following drawing.
4. Consult proper tables for the quantity of air.
If the total external static pressure exceeds the maximum
listed on the furnace rating plate, check for closed damp-
ers, registers, undersized and/or oversized poorly laid out
duct work.
The temperature rise of the furnace must be within the
temperature rise range listed on the furnace rating plate.
Digital
Manometer
Checking Static Pressure
(80% Furnace Shown, 90% Similar)

E
DGES
OF
SHEET
METAL
HOLES
MAY
BE
SHARP
. U
SE
GLOVES
AS
A
PRECAUTION
WHEN
REMOVING
SHEET
METAL
FROM
RETURN
AIR
OPENINGS
.
WARNING

        
“lance and cut” method to remove sheet metal from the duct
opening in the base pan. To remove, simply press out the lanced
sections by hand to expose the metal strips retaining the sheet
metal over the duct opening. Using tin snips, cut the metal
strips and remove the sheet metal covering the duct opening.
In the corners of the opening, cut the sheet metal along the


perimeter of the opening using a pair of seamer pliers or seamer
tongs. -

performance issues and noise issues.
CUT FOUR CORNERS
AFTER REMOVING SHEET
METAL
CUT USING TIN SNIPS
PRESS OUT BY HAND
SCRIBE LINES OUTLINING
DUCT FLANGES

