Instructions / Assembly

16
AIRFLOW DATA (CFM) - Table 10
16 Airflow Data
0.1 0.2 0.3 0.4 0.5 0.6 0.7
LOW 650 620 595 540 490 420 275
MED 885 865 825 815 750 690 560
HIGH 1255 1225 1130 1090 965 925 800
LOW 650 620 595 540 490 420 275
MED 885 865 825 815 750 690 560
HIGH 1255 1225 1130 1090 965 925 800
LOW 660 625 595 560 500 430 330
MED 930 905 865 820 765 700 590
HIGH 1235 1185 1130 1060 990 910 825
LOW 1120 1085 1040 1000 940 875 800
MED 1425 1385 1345 1285 1220 1145 1060
HIGH 1625 1575 1520 1460 1375 1295 1200
LOW 1120 1085 1040 1000 940 875 800
MED 1425 1385 1345 1285 1220 1145 1060
HIGH 1625 1575 1520 1460 1375 1295 1200
LOW 1295 1255 1225 1175 1120 1055 970
MED 1535 1485 1420 1370 1295 1215 1130
HIGH 1755 1680 1590 1515 1425 1340 1250
LOW 1155 1115 1070 1015 955 895 840
MED 1505 1470 1430 1375 1300 1210 1105
HIGH 1785 1735 1680 1625 1555 1440 1330
LOW 1410 1360 1290 1210 1120 1010 920
MED 1610 1540 1470 1390 1300 1190 1060
HIGH 1900 1830 1740 1645 1540 1420 1280
LOW 1420 1370 1310 1240 1125 1045 960
MED 1625 1585 1515 1435 1350 1235 1095
HIGH 1930 1890 1820 1735 1635 1505 1355
LOW 1410 1360 1290 1210 1120 1010 920
MED 1610 1540 1470 1390 1300 1190 1060
HIGH 1900 1830 1740 1645 1540 1420 1280
LOW 1530 1500 1460 1405 1350 1280 1155
MED 1950 1885 1830 1785 1745 1670 1595
HIGH 2235 2170 2100 2030 1965 1915 1825
Notes
ARUF47D14
Model
Blower
Speed
Static Pressure (in w.c) Airflow (CFM)
ARUF25B14
ARUF29B14
ARUF31B14
ARUF49D14
ARUF61D14
1. Airflow data indicated is at 230V without air filter in place.
2. The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on
3. Use the CFM adjustment factors of 0.98 for horizontal left and 0.96 for horizontal right & downflow orientations
ARUF37C14
ARUF43C14
ARUF49C14
ARUF37D14
ARUF43D14