Instructions / Assembly

17
ASPT AIRFLOW DATA (CFM) - Table 11
Notes
3. Use the CFM ad
j
ustment factors of 0.98 for horizontal left and 0.96 for horizontal ri
g
ht & downflow orientations.
1. Airflow data indicated is at 230V without air filter in
p
lace.
2. The chart is for information onl
y
. For satisfactor
y
o
p
eration
,
external static
p
ressure must not exceed value shown on ratin
g
p
late. The shaded area
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
T1 640 585 580 545 510 490 410 340 280
T2 800 765 725 700 670 645 595 565 490
T3 840 805 800 760 740 700 670 625 580
T4 985 950 920 885 850 815 800 760 725
T5 1475 1440 1400 1375 1335 1305 1270 1240 1150
T1 595 590 565 530 505 455 380 305 260
T2 790 775 745 705 665 625 585 515 445
T3 865 820 790 770 735 695 645 595 530
T4 1015 980 955 925 880 840 795 770 720
T5 1505 1465 1430 1410 1385 1350 1315 1285 1220
T1 875 845 845 825 795 780 730 680 630
T2 985 945 925 915 905 880 845 795 760
T3 1070 1025 990 985 980 960 940 905 860
T4 1245 1205 1170 1135 1115 1115 1100 1090 1035
T5 1310 1275 1230 1190 1155 1135 1085 1080 1040
T1 1025 985 945 910 875 830 795 735 690
T2 1150 1105 1065 1025 995 950 915 870 825
T3 1240 1200 1160 1120 1085 1050 1010 970 925
T4 1425 1400 1355 1320 1290 1250 1215 1180 1145
T5 1490 1455 1415 1390 1355 1320 1285 1250 1205
T1 865 685 615 540 480 410 335 270 215
T2 935 880 820 785 720 660 600 550 490
T3 1110 1050 1000 955 905 855 795 760 710
T4 1360 1310 1260 1220 1180 1135 1095 1055 1010
T5 1560 1515 1475 1435 1395 1370 1330 1295 1260
T1 980 935 895 860 825 800 755 710 665
T2 1125 1075 1045 1000 965 930 880 845 820
T3 1235 1190 1155 1120 1085 1045 1005 965 920
T4 1485 1450 1425 1390 1355 1315 1275 1230 1190
T5 1565 1535 1510 1480 1240 1390 1365 1320 1280
T1 865 685 615 540 480 410 335 270 215
T2 935 880 820 785 720 660 600 550 490
T3 1110 1050 1000 955 905 855 795 760 710
T4 1360 1310 1260 1220 1180 1135 1095 1055 1010
T5 1560 1515 1475 1435 1395 1370 1330 1295 1260
T1 955 895 855 840 780 735 675 615 560
T2 1100 1050 1005 965 925 870 815 770 705
T3 1205 1160 1120 1075 1035 990 940 885 830
T4 1445 1410 1365 1320 1275 1235 1190 1140 1095
T5 1525 1480 1435 1400 1360 1320 1275 1230 1180
T1 1325 1280 1240 1200 1160 1115 1065 1025 990
T2 1465 1420 1380 1355 1315 1280 1245 1195 1155
T3 1510 1470 1430 1395 1355 1330 1290 1250 1210
T4 1600 1565 1530 1490 1460 1425 1390 1365 1295
T5 1690 1660 1625 1590 1555 1525 1490 1400 1255
T1 1370 1330 1295 1255 1215 1180 1140 1100 1060
T2 1535 1500 1465 1430 1405 1370 1335 1300 1210
T3 1680 1645 1615 1575 1545 1510 1440 1330 1205
T4 1905 1855 1780 1690 1605 1515 1425 1330 1205
T5 1940 1855 1775 1700 1605 1505 1420 1320 1205
T1 1055 1015 950 895 830 785 730 680 620
T2 1210 1165 1110 1070 1015 960 900 840 785
T3 1335 1290 1250 1205 1145 1100 1050 980 910
T4 1625 1580 1530 1495 1455 1405 1350 1295 1230
T5 1720 1670 1625 1580 1540 1490 1435 1390 1325
T1 1485 1435 1380 1320 1265 1200 1230 1015 930
T2 1570 1525 1480 1430 1370 1315 1235 1155 1035
T3 1680 1600 1570 1555 1475 1430 1360 1280 1185
T4 1800 1765 1715 1670 1625 1590 1510 1465 1390
T5 2215 2160 2120 2085 2040 2000 1970 1930 1865
T1 1545 1495 1440 1390 1335 1260 1180 1105 1045
T2 1705 1655 1605 1555 1505 1445 1380 1330 1275
T3 1850 1805 1760 1710 1665 1615 1555 1500 1445
T4 2095 2055 2020 1980 1935 1890 1845 1800 1755
T5 2260 2205 2195 2160 2120 2075 2030 1990 1945
ASPT61D14A
A
ASPT37B14AA
ASPT37C14AA
ASPT47C14AA
ASPT59C14AA
ASPT47D14AA
ASPT49D14AA
ASPT39C14AA
ASPT49C14AA
ASPT33C14AA
ASPT35B14AA
Model Blower Speed
Static Pressure (in w.c.) Airflow (CFM)
ASPT25B14AA
ASPT29B14AA