Use and Care Manual
SS-GARUF www.goodmanmfg.com 3
ARUF
25B14*
ARUF
29B14*
ARUF
31B14*
ARUF
37C14*
ARUF
43C14*
ARUF
49C14*
ARUF
37D14*
ARUF
43D14*
ARUF
47D14*
ARUF
49D14*
ARUF
61D14*
Cooling (Btu/h) 24,000 25,000 30,000 36,000 42,000 48,000 36,000 42,000 43,000 48,000 60,000
Piston Size 0.051 0.057 0.065 0.072 0.076 0.080 0.072 0.076 0.076 0.080 0.080
Diameter 9½" 9½" 9½" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝" 11
15
/
16
"
Width 6" 6" 6" 8" 8" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝"
Liquid
⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜"
Sucon
¾" ¾" ⅞" ⅞" ⅞" ⅞" ⅞" ⅞" ⅞" ⅞" ⅞"
Coil Drain Connect (FPT)
¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾"
Voltage 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Min Circuit Ampacity 2.4/2.4 2.4/2.4 2.4/2.4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 6/6
Max. Overcurrent Device (Amps) 15/15 15/15 15/15 15/15 15/15 15/15 15/15 15/15 15/15 15/15 15/15
Minimum VAC
197 197 197 197 197 197 197 197 197 197 197
Maximum VAC
253 253 253 253 253 253 253 253 253 253 253
Full Load Amps (FLA)
1.9 1.9 1.9 3.0 3.0 3.1 3.0 3.5 3.5 3.5 4.6
Horsepower (HP)
⅓ ⅓ ⅓ ⅓ ⅓ ½ ⅓ ½ ½ ½ ¾
100 100 110 130 130 135 140 145 150 145 155
For a properly matched system and piston sizing informaon, refer to Amana piston kit chart of the corresponding Amana® outdoor unit.
Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protecon (MOP) for blower without supplemental heat installed.
Refer to unit nameplate and/or Heat Kit Data for specicaon with approved accessory heaters installed.
Product Specifications