Instructions / Assembly

28
5. Turn ON the gas supply.
6. Turn on power and close thermostat “R” and “W1”
contacts to provide a call for low stage heat.
7. Measure the gas manifold pressure with burners firing.
Adjust manifold pressure using the Manifold Gas
Pressure table shown below.
8. Remove regulator cover screw from the low (LO) outlet
pressure regulator adjust tower and turn screw clockwise
to increase pressure or counterclockwise to decrease
pressure. Replace regulator cover screw.
9. Close thermostat “R” and “W2” contacts to provide a
call for high stage heat.
10. Remove regulator cover screw from the high (HI) outlet
pressure regulator adjust tower and turn screw clockwise
to increase pressure or counterclockwise to decrease
pressure. Replace regulator cover screw.
11. Turn off all electrical power and gas supply to the system.
12. Remove the manometer hose from the hose barb fitting
or outlet pressure tap.
13. Replace outlet pressure tap:
a. Honeywell valve: Remove the 1/8" NPT hose barb fitting
from the outlet pressure tap. Replace the outlet
pressure tap plug and seal with a high quality thread
sealer.
b. White-Rodgers valve: Turn outlet pressure test screw
in to seal pressure port (clockwise, 7 in-lb minimum).
14. Turn on electrical power and gas supply to the system.
15. Close thermostat contacts “R” and “W1/W2” to energize
the valve.
Using a leak detection solution or soap suds, check for leaks
at outlet pressure tap plug (Honeywell valve) or screw (White-
Rodgers valve). Bubbles forming indicate a leak. SHUT OFF
GAS AND REPAIR ALL LEAKS IMMEDIATELY!
NOTE: For gas to gas conversion, consult your dealer for
appropriate conversion.
Range Nominal
Natural Low Stage 1.6 - 2.2" w .c. 1.9" w .c.
High Stage 3.2 - 3.8" w .c. 3.5" w .c.
Propane Low Stage 5.7 - 6.3" w .c. 6.0" w .c.
High Stage 9.7 - 10.3" w .c. 10.0" w .c.
Manifold Gas Pressure
Gas
NOTE: Airflow data shown applies to legacy mode operation only. For a fully communicating system, please see the
outdoor unit’s installation instructions for cooling and pump heating airflow data. See ComfortNet™ System - Airflow
Consideration section for details.
continuous fan speeds (25%, 50%, 75%, or 100%). " See installation manual
for details"
*theS” number refers to one of four labeled dip switch section each containing 4
individual dip switches. The following number refers to the individual labeled dip
switch within that section
Model Tap Low Stage High Stage Low Stage High Stage
Cool Cool Heat Heat
A 520 800 1210 1725
B 715 1100 1225 1750
C 910 1400 1245 1775
D 1170 1800 1260 1800
A 553 850 1085 1550
B 748 1150 1155 1650
C 943 1450 1225 1750
D 1203 1850 1260 1800
A 390 600 875 1250
B 520 800 945 1350
C 715 1100 1015 1450
D 910 1400 1085 1550
A 390 600 735 1050
B 520 800 805 1150
C 650 1000 875 1250
D 780 1200 945 1350
A 520 800 945 1350
B 715 1100 1015 1450
C 910 1400 1085 1550
D 1170 1800 1155 1650
A 520 800 1050 1500
B 715 1100 1120 1600
C 910 1400 1190 1700
D 1170 1800 1260 1800
Speed Selection Dip Switches
the corresponding tap (A, B, C, or D). Set dip switches S3-1* and S3-2* to the
appropriate ON / OFF positions. (2) Select model and desired High Stage Heating
Airflow. Determine the corresponding tap (A, B, C, or D). Set dip switches S4-3* and
S4-4* to the appropriate ON / OFF positions. (3) Selecting Airflow Adjustment Factor:
For 0% trim set S5-2* to OFF (trim disabled). If trim is desired set S5-2* to ON (trim
enabled) and set S3-3* and S3-4* to appropriate ON / OFF positions. Tap A is +5%,
Tap B is -5%, Tap C i s +10 %, Tap D i s -10%.
To Set Comfort Mode: Select Desired Comfort Mode profile (see profiles above). Set
Profiles Pre-Run Short-Run OFF Delay
Cool Adjust Profile Heat
Selection Selection Selection Selection
Switches Switches Switches Switches
A OFF OFF OFF OFF OFF OFF OFF OFF
Dehumidification: To enable, set switch S5-1* to ON. Cooling airflow will be reduced
to 85% of nominal value during cool call. To disable, set switch S5-1* to OFF.
D 30 sec/50% 7.5 min/82% 30 sec/50%
D ON ON ON ON ON ON ON ON
B ------- 30 sec/50% 60 sec/100%
C OFF ON OFF ON OFF ON OFF ON
B ON OFF ON OFF ON OFF ON OFF
TAP S3- 1 S3- 2 S3- 3 S3- 4 S4-1 S4-2 S4- 3 S4- 4
dip switches S4-1* and S4-2* to the appropriate ON / OFF positions.
A ------- -------- 60 sec/100%
C ------- 7.5 min/82% 60 sec/100%
To Set Airflow: (1) Select model and desired High Stage Cooling Airflow. Determine
*DVC81005C***
*DVC80805C***
*DVC80603B***
*MVC81005C***
*MVC80805C***
Continuous Fan Speed: Set dip switches S5-3* and S5-4* to select one of 4
0140F01170
*MVC80604B***