Electric Heat Airflow & Dipswitch Settings
HTR kW 9 10 11
AVPTC
24B14
AVPTC
25B14
AVPTC
29B14
AVPTC
30C14
AVPTC
31C14
AVPTC
36C14
AVPTC
37B14
AVPTC
37C14
AVPTC
37D14
3 ON ON ON 730 550 550 730 --- NR 550 --- ---
5 ON ON OFF 780 650 650 780 850 850 650 850 1240
6 ON OFF ON 850 700 700 850 900 900 700 900 1240
8 ON OFF OFF 950 800 800 950 1000 1000 800 1000 1240
10 OFF ON ON 1025 850 875 1025 1170 1200 875 1170 1240
15 OFF ON OFF NR 875 875 NR 1345 1440 1050 1345 1520
19* OFF OFF ON NR --- --- NR 1345 1500 --- 1345 ---
20 NR --- --- NR --- 1500 --- --- 1520
21 or 25* OFF OFF OFF NR --- --- NR --- NR --- --- ---
Note: Airow data shown applies to the electric heat only in either legacy mode or communicang mode operaon
--- indicates Not Rated
* Within thermostat user menu, CTK0* communicang thermostat will display 20kW for OFF- OFF- ON dipswitch selecon,
21kW for OFF-OFF-OFF dipswitch selecon.
For match up with a 2 ton outdoor unit: Heater kit applicaon shall not exceed 10 kW.
Airow for 5 kW up to 10 kW heater kits shall be set to 850 cfm speed tap of ON-ON-ON.
†† For match up with a 3 ton outdoor unit: Heater kit applicaon shall not exceed 15 kW.
Airow for 5 kW up to 15 kW heater kits shall be set to 1300 cfm speed tap of ON-OFF-ON.
††† For match up with a 3.5 ton outdoor unit: Heater kit applicaon shall not exceed 20 kW.
Airow for 5 kW up to 20 kW heater kits shall be set to 1500 cfm speed tap of ON-OFF-OFF
** 3 kW heater kit is not applicable for this indoor applicaon.
HTR kW 9 10 11
AVPTC
42D14†
AVPTC
48C14
AVPTC
48D14††
AVPTC
49D14 ƚƚ
AVPTC
59C14
AVPT
C59D14
AVPTC
60D14†††
AVPTC
61D14 ƚƚƚ
3 ON ON ON
850** NR NR --- --- --- NR ---
5 ON ON OFF 1400 850 1400 1250 1170 1240 1620 1250
6 ON OFF ON 1630 900 1630 1300 1170 1240 1670 1300
8 ON OFF OFF 1630 1000 1630 1500 1170 1240 1720 1500
10 OFF ON ON 1670 1200 1670 1550 1170 1240 1750 1550
15 OFF ON OFF 1720 1440 1720 1720 1345 1520 1780 1780
19* OFF OFF ON NR 1500 NR --- 1345 --- NR ---
20 1800 1500 1815 --- --- 1520 1850 1850
21 or 25* OFF OFF OFF NR NR 1850 --- --- --- 1850 1850
Note: Airow data shown applies to the electric heat only in either legacy mode or communicang mode operaon
--- indicates Not Rated
* Within thermostat user menu, CTK0* communicang thermostat will display 20kW for OFF- OFF- ON dipswitch selecon,
21kW for OFF-OFF-OFF dipswitch selecon.
For match up with a 2 ton outdoor unit: Heater kit applicaon shall not exceed 10 kW.
Airow for 5 kW up to 10 kW heater kits shall be set to 850 cfm speed tap of ON-ON-ON.
†† For match up with a 3 ton outdoor unit: Heater kit applicaon shall not exceed 15 kW.
Airow for 5 kW up to 15 kW heater kits shall be set to 1300 cfm speed tap of ON-OFF-ON.
††† For match up with a 3.5 ton outdoor unit: Heater kit applicaon shall not exceed 20 kW.
Airow for 5 kW up to 20 kW heater kits shall be set to 1500 cfm speed tap of ON-OFF-OFF
** 3 kW heater kit is not applicable for this indoor applicaon.