GSX14 Service Manual

51
ACCESSORIES
ELECTRIC HEAT KIT APPLICATIONS - AVPTC
* Revision level that may or may not be designated.
C Circuit breaker option.
ELECTRIC HEAT KIT APPLICATIONS - AEPF
NOTE:
When 8kW and 10kW heat kits are used with an AVPTC1830 and AVPTC3137, matched with 2- ton outdoor unit, see Note 1 below.
1
Set Heater Kit dip switches 9, 10 and 11 to 6kW setting (9-ON, 10-OFF,11-ON) to obtain 840 CFM.
2
This heater kit can only be used for ‘1000 CFM or higher’ applications.
3
This heater kit can only be used for ‘1200 CFM or higher’ applications.
ELECTRIC HEAT KIT APPLICATIONS - ADPF
ADPF182416 ADPF304216 ADPF486016 ADPF4486016
HKR-03* X X X X
HKR-05*, HKR-05C* X X X X
HKR-06* X X X X
HRK-08*, HKR-08C* X
1
X
1
X
1
X
HKR-10*, HKR-10C*
X
1
X
1
X
1
X
HKA-15C*
XX
X
2
X
1
HKA-20C*
-X
X
2
X
1
^HKR3-15*
-X
XX
^HKR3-20*
-X
XX
*
Revision level that may or may not be designated
1
Air handler must be on speed tap 2, 3, 4 or 5
C Circuit Breaker option
2
Air handler must be on speed tap 4 or 5
^ Heat kit requires 3-phase power supply
3
Air handler must be on speed tap 3, 4 or 5
AEPF183016 AEPF303616 AEPF313716 AEPF426016
HKR-05*, HKR-05C* X X
HRK-08*, HKR-08C X X X
HKR-10*, HKR-10C
X
1
XXX
HKA-15C* X
1
X
1
X
HKA-20C*
X
2
*
Revision level that may or may not be designated
C Circuit Breaker option
1
This heater kit can be used ONLY for 1000 CFM or higher applications
2
This heater kit can be used ONLY for 1200 CFM or higher applications
MODELS
HKR-03*
HKR-05*/-05C
*
HKR-06*
HKR-08*/-08C
*
HKR-10*/-10C
*
HKA-15C*
HKA-20C*
AVPTC183014A* X X X
X
1
X
1
--- ---
AVPTC313714A* X X X
X
1X1
X
2
X
AVPTC426014A* X X X X X X
X
3