GSX14 Service Manual

SERVICING
83
Symptoms of Abnormal Operation
(Legacy & ComfortNet Thermostat)
Diagnostic/Status LED Codes
Faul t
Description
Co mf o rt Net
Thermostat Only
Possible Causes
Corrective Actions Notes & Cautions
Green Yel lo w Red Red Y1 Message Code
Very long run time.
Four consecutive compressor protector
trips with average run time between
trips greater than 3 hours.
Compressor operating at high speed
and out door fan operating at low speed
Integrated control module
diagnostic/status LEDs displ ay the
indicated code.
OFF 1 Flash OFF ON if call
present;
OFF if no
call
Low Side Fault. LOW S IDE
FA ULT
01 Low refrigerant charge.
Restriction in liquid line.
Indoor bl ower motor
failure.
Indoor thermostat set
extremely low.
Verify refrigerant
charge; adjust as
needed.
Check for restricted
liquid line;
repair/replace as
needed.
Check indoor blower
motor; repair/replace
as needed.
Check indoor
thermostat setting.
Turn power OFF prior
to repair.
Fault will c lear after 30
consecutive normal
cycles.
Fault may be cleared by
cycling 24VAC to
control.
Replace with correct
replacement part(s).
Compressor a nd out door fan are off.
Thermostat demand is present.
Integrated control module
diagnostic/status LEDs displ ay the
indicated code.
ON 1 Flash OFF ON if cal l
present;
OFF if no
call
Low Pressure
CO Trip.
LPS OPEN 01
Low refrigerant charge.
Restriction in liquid line.
Indoor bl ower motor
failure.
Indoor thermostat set
extremely low.
Verify refrigerant
charge; adjust as
needed.
Check for restricted
liquid line;
repair/replace as
needed.
Check indoor blower
motor; repair/replace
as needed.
Check low pressure
switch; repair/replace
as needed.
Check indoor
thermostat setting.
Turn power OFF prior
to repair.
Replace with correct
replacement part(s).
Compressor a nd out door fan are off.
Low pressure switch trip 3 times within
same thermostat demand.
Thermostat demand is present.
Integrated control module
diagnostic/status LEDs displ ay the
indicated code.
ComfortNet™ thermostat “Call for
Service” icon illuminated.
ComfortNet™ thermostat scrolls
Check Air Condi ti one r” orCheck
Heat Pump” message.
ON 1 Flash ON ON if call
present;
OFF if no
call
LPCO Lockout
(3 Trips).
LPS
LOCKOUT
01
Low refrigerant charge.
Restriction in liquid line.
Indoor bl ower motor
failure.
Indoor thermostat set
extremely low.
Verify refrigerant
charge; adjust as
needed.
Check for restricted
liquid line;
repair/replace as
needed.
Check indoor blower
motor; repair/replace
as needed.
Check low pressure
switch; repair/replace
as needed.
Check indoor
thermostat setting.
Turn power OFF prior
to repair.
Must clear fault by
cycling 24VAC to
control.
Replace with correct
replacement part(s).