GSX14 Service Manual

SERVICING
87
Diagnostic/Status LED Codes
Com f o r tNet
Thermostat Only
Symptoms of Abnormal Operation
(Legacy & ComfortNet™ Thermostat)
Green Yell ow Red Red Y1
Fault
Description
Mess a ge Code
Possi ble Causes
Corrective Actions Not es & Cauti ons
Air co nditi oner/ heat pump may appear
to be operating normally.
Integrated control module
diagnostic/status LEDs display the
indicated code.
OFF 9
Fl ash e s
OFF ON if call
present;
OFF i f no
call
Low Pilot
Voltage
LOW
SECOND
VOLT
09 Control detects secondary
voltage less than 18 VAC.
Transformer overloaded.
Low line vol tage.
Check fuse.
Correct low secondary
voltage condition.
Check transformer;
replace if needed.
Turn power OFF prior
to repair.
Fault will clear if
secondary voltage rises
above 21VAC.
Replace with correct
replacement part(s).
Compressor is off.
Integrated control module
diagnostic/status LEDs display the
indicated code.
OFF ON ON ON if call
present;
OFF i f no
call
Comp Protector
Open
Not di sp layed
Not
displ aye d
No current through run or
start wi ndings.
Compressor run wi ndi ng
is ope n.
Compressor not properl y
wired to control.
Faulty compressor wiring.
Failed compressor run
capacitor.
Faulty run capacitor
wir i n g.
Check compressor;
repair/replace as
needed.
Check wiring;
repair/replace as
needed.
Check run capacitor;
replace as needed.
Turn power OFF prior
to repair.
Fault will clear after 1
no r mal cycle.
Fault may be cleared by
cycling 24VAC to
control.
Replace with correct
replacement part(s).