GSX14 Service Manual

SERVICING
95
0140M00407-A
7 SEGMENT LED
(DS2)
7 SEGMENT LED
(DS1)
DESCRIPTION OF CONDITION
0 n Standby
0 1 Low Pressure CO Trip
0 1 Low Side Fault
0 2 High Pressure CO Trip
0 2 High Side Fault
0 3 Short Cycling
0 4 Locked Rotor
0 5 Open Circuit
0 6 Open Start Circuit
0 7 Open Run Circuit
0 8 No Line Voltage
0 9 Low Pilot Voltage
88 Power Up
A 2 Outdoor Air Temp Sensor Fault
A 3 Outdoor Coil Temp Sensor Fault *
b 0 No Indoor Airflow
b 9 Inadequate Airflow
C 3 Cool Mode Short Cycle Timer
C 1 Low Cool
C 2 High Cool
dF Defrost *
d t Max Defrost Time *
d E Forced Defrost *
d 0 Data not yet on Netw ork
d 1 Invalid Data on Netw ork
d 2 System Mis-Match
d 3 Configuration Mis-Match
d 4 Invalid Memory Card Data
E E Board Misoperation
E 5 Open Fuse
F t Field Test Mode
H 8 High Line Voltage
L 1 LPCO Lockout (3 Trips)
L 2 HPCO Lockout (3 Trips)
L 6 Open Start Circuit Lockout
L 7 Open Run Circuit Lockout
L 8 Low Line Voltage
P 3 Heat Mode Short Cycle Timer *
P 1 Low Heat *
P 2 High Heat *
P 0 Comp Protector Open
Pd Pump Down
* CODE USED ON HEAT PUMP MODELS ONLY
NOTE 1: DS1, DS2 AND DS3 ARE LABELED ON THE CONTROL ABOVE EACH 7
SEGMENT LED DISPLAY
NOTE 2: 7 SEGMENT LED DISPLAY DS3 IS NOT USED
PCBHR104