Service Manual
SERVICING
49
As more and more electronic's are introduced to the Heat-
ing Trade, Polarization of incoming power and phasing of
primary to secondary voltage on transformers becomes
more important.
Polarization has been apparent in the Appliance industry
since the introduction of the three prong plug, however, the
Heating Industry does not use a plug for incoming power,
but is hard wired.
Some of the electronic boards being used today, with flame
rectification, will not function properly and/or at all without
polarization of incoming power. Some also require phasing
between the primary and secondary sides of step-down
transformers.
THIS IS L1 OR THE 
 HOT POWER LEG
INCOMING POWER
THIS IS THE COMMON
 OR NEUTRAL LEG
METER READS 
 120 VOLTS
METER READS 
 0 VOLTS
GND
GND
VOLT / OHM
 METER
VOLT / OHM
 METER
These then should be wired to the furnace accordingly.
CHECKING FOR PHASING - PRIMARY TO SECONDARY OF UNMARKED TRANSFORMERS*
If meter reads approximately 96 volts - the primary to secondary are in phase - if reads approximately 144 volts out of
phase - reverse low voltage wires.
*NOTE: For flame rectification the common side of the secondary voltage (24 V) is cabinet grounded. If you were to bench
test a transformer the primary neutral and secondary common must be connected together for testing purposes.
Some transformers will display phasing symbols as shown
in the illustration to the left to assist in determining proper
transformer phasing.
Checking for polarization and phasing should become a
habit in servicing. Let's start now.
NOTE: Newer integrated ignition controls have a diagnos-
tic flash code for reversed polarity (Refer to Troubleshoot-
ing-Diagnostic Chart for LED Codes).
.
.
.
.
.
.
VOLT / OHM
 METER
G
N
D
PRIMARY
SECONDARY
TRANSFORMER
R
C
METER READS
  24 VOLTS
LINE VOLTAGE
 (NEUTRAL)
LINE VOLTAGE
 L1 (HOT)
VOLT / OHM
 METER
METER READS
 120 VOLTS
VOLT / OHM
 METER
C
R
G
N
D
N
L1
V
OLT / OHM
 METER
READS 96 VOLTS - IN PHASE
C
R
G
N
D
N
L1
V
OLT / OHM
 METER
READS 144 VOLTS - OUT OF PHASE
C
R
G
N
D
NEUTRAL
L1
PHASING SYMBOL
24 V
120 V