TROUBLESHOOTING CODES
Message Code
Furn ace f ails to operate on high
stage; f u rnace operates normally on
low stage.
Integrated control module LED
display provides
E8
error code.
E8
High stage
pressure switch
circuit is closed
at start of
heating cycle.
Induced draft
blower is
operating.
Fu rn ace is
operating on
low stage on l y
PS2
CLOSED
E8
High stage pressure switch
contacts sticking.
Shorts in pressure switch circuit
wiring.
Replace high stage pressure switch.
Repair short in wiring
Turn power OFF prior to repair.
Replace p ressure swi tch wi th correct
replacement part.
Furn ace f ails to operate on high
stage; f u rnace operates normally on
low stage.
Integrated control module LED
display provides
E9
error code.
E9
High stage
pressure switch
circuit is not
closed.
Induced draft
blower is
operating.
Fu rn ace is
operating on
low stage on l y
PS2
OPEN
E9
Pressure switch hose blocked
pinched, or connected improperly.
Blocked flue and/or inlet air pipe,
blocked drain system or weak
induced draft blower.
Incorrect pressure switch set point
or malfunctioning switch contacts.
Loose or improperly connected
wiring.
Inspect pressure switch hose.
Repair/replace if necessary.
Inspect flue and/or inlet air piping for
blockage, proper length, elbows, and
termination. Check drain system.
Correct as necessary.
Check induced draft blower
performance. Correct as necessary.
Correct pressure switch set point or
contact motion.
Tighten or correct wiring connection.
Turn power OFF prior to repair.
Replace p ressure swi tch wi th correct
replacement part.
Replace ind uced draf t blower with
correct replacement part.
Furn ace f ails to operate.
Integrated control module LED
display provides
EA
error code.
ComfortNet thermostat “ Call for
Service icon illuminated.
ComfortNet thermostat scrolls
Check Furnace messag e.
EA
Polarity of
115 v o l t A C i s
reversed
REVERSED
PLTY
EA
Polarity of 115 volt AC power to
furnace or integrated module is
reversed.
Reversed unit ground.
Review wiring diagram to correct
polarity.
Verify proper ground. Correct if
necessary.
Check and correct wiring.
Turn power OFF prior to repair.
Furn ace f ails to operate.
Integrated control module LED
display provides
d0
error code.
ComfortNet thermostat “ Call for
Service icon illuminated.
ComfortNet thermostat scrolls
Check Furnace messag e.
d0
•Data not yet
on network.
NO NET
DAT A
d0 Furnace does not contain any
shared data.
Populate shared data set using
memory card.
Turn power OFF prior to repair.
Use memory card for the specific
model.
Insert memory card BEFORE turning
power ON. Memory card may be
removed after data is loaded.
Turn power OFF before removing
memory card.
Error code will be cleared once data
is loaded.
Operation diff erent than expected or
no operation.
Integrated control module LED
display provides
d4
error code.
ComfortNet thermostat “ Call for
Service icon illuminated.
ComfortNet thermostat scrolls
Check Furnace messag e.
d4
Invalid memory
card data.
INVALID MC
DAT A
d4 Shared data set on memory card
has been rejected by integrated
control module
Verify shared data set is correct for
th e specif ic model. Re-populate
data using correct memory card if
required.
Turn power OFF prior to repair
Use memory card for the specific
model.
Insert memory card BEFORE turning
power ON. Memory card may be
removed after data is loaded.
Turn power OFF before removing
memory card.
Error code will be cleared once data
is loaded.
Symptoms of Abnormal Operation
(Non-communicating
& ComfortNet™ Thermostat)
ComfortNet
Thermostat Only
Possible Causes Corrective Actions Notes & Cautions
Diagnostic
& Status
LED Codes
Fault