Service Instructions

SERVICING
119
S-115 COMPRESSOR BURNOUT
When a compressor burns out, high temperature develops caus-
ing the refrigerant, oil and motor insulation to decompose
forming acids and sludge.
If a compressor is suspected of being burned-out, attach a
refrigerant hose to the liquid line dill valve and properly remove
and dispose of the refrigerant.
NOTICE
Violation of EPA regulations may result in fines
or other penalties.
Now determine if a burn out has actually occurred. Confirm by
analyzing an oil sample using a Sporlan Acid Test Kit, AK-3 or its
equivalent.
Remove the compressor and obtain an oil sample from the
suction stub. If the oil is not acidic, either a burnout has not
occurred or the burnout is so mild that a complete clean-up is not
necessary.
If acid level is unacceptable, the system must be cleaned by using
the clean-up drier method.
Do not allow the sludge or oil to contact the skin.
Severe burns may result.
CAUTION
NOTE: The Flushing Method using R-11 refrigerant is no longer
approved by Amana
®
Brand Heating-Cooling.
Suction Line Drier Clean-Up Method
The POE oils used with R410A refrigerant is an excellent solvent.
In the case of a burnout, the POE oils will remove any burnout
residue left in the system. If not captured by the refrigerant filter,
they will collect in the compressor or other system components,
causing a failure of the replacement compressor and/or spread
contaminants throughout the system, damaging additional com-
ponents.
Install a field supplied suction line drier. This drier should be
installed as close to the compressor suction fitting as possible.
The filter must be accessible and be rechecked for pressure drop
after the system has operated for a time. It may be necessary to
use new tubing and form as required.
NOTE: At least twelve (12) inches of the suction line immediately
out of the compressor stub must be discarded due to burned
residue and contaminates.
1. Remove compressor discharge line strainer.
2. Remove the liquid line drier and expansion valve.
3 Purge all remaining components with dry nitrogen or carbon
dioxide until clean.
4. Install new components
including liquid line drier.
5. Braze all joints, leak test, evacuate, and recharge system.
6. Start up the unit and record the pressure drop across the
drier.
7. Continue to run the system for a minimum of twelve (12) hours
and recheck the pressure drop across the drier. Pressure
drop should not exceed 6 PSIG.
8. Continue to run the system for several days, repeatedly
checking pressure drop across the suction line drier. If the
pressure drop never exceeds the 6 PSIG, the drier has trapped
the contaminants. Remove the suction line drier from the
system.
9. If the pressure drop becomes greater, then it must be replaced
and steps 5 through 9 repeated until it does not exceed 6 PSIG.
NOTICE: Regardless, the cause for burnout must be determined
and corrected before the new compressor is started.
S-120 REFRIGERANT PIPING
The piping of a refrigeration system is very important in relation
to system capacity, proper oil return to compressor, pumping
rate of compressor and cooling performance of the evaporator.
POE oils maintain a consistent viscosity over a large tempera-
ture range which aids in the oil return to the compressor;
however, there will be some installations which require oil
return traps. These installations should be avoided whenever
possGible, as adding oil traps to the refrigerant lines also
increases the opportunity for debris and moisture to be
introduced into the system. Avoid long running traps in
horizontal suction line.
S-201 CLEANING ALUMINUM COILS
This unit is equipped with an aluminum tube evaporator coil. The
safest way to clean the evaporator coil is to simply flush the coil
with water. This cleaning practice remains as the recommended
cleaning method for both copper tube and aluminum tube resi-
dential cooling coils.
An alternate cleaning method is to use one of the products listed
in the technical publication TP-109 (shipped in the literature bag
with the unit) to clean the coils. The cleaners listed are the only
agents deemed safe and approved for use to clean round tube
aluminum coils. TP-109 is available on the web site in Partner
Link > Service Toolkit.
NOTE: Ensure coils are rinsed well after use of any chemical cleaners.