GSZH5 Service Manual

93
SERVICING
WARNING

7. Remove the wiring from the control terminals.
8. Using an ohmmeter test for continuity across the
normally closed contacts. No reading indicates the
control is open - replace if necessary. Make sure the
limits are cool before testing.
If Found Open - Replace - Do Not Wire Around.

Optional electric heaters may be added, in the quantities
shown in the spec sheet for each model unit, to provide
electric resistance heating. Under no condition shall more
heaters than the quantity shown be installed.
WARNING





1. Disassemble and remove the heating element(s).
2. Visually inspect the heater assembly for any breaks in
the wire or broken insulators.
3. Using an ohmmeter, test the element for continuity -
no reading indicates the element is open. Replace as
necessary.

Optional electric heaters may be added, in the quantities

resistance heating. Under no condition shall more heaters
than the quantity shown be installed.
The low voltage circuit in the air handler is factory wired
and terminates at the location provided for the electric

the installation.
Other components such as a Heating/Cooling Thermostat
and Outdoor Thermostats are available to complete the
installation.
The system CFM can be determined by measuring the
static pressure external to the unit. The installation manual
supplied with the blower coil, or the blower performance
table in the service manual, shows the CFM for the static
measured.
Alternately, the system CFM can be determined by
operating the electric heaters and indoor blower WITHOUT
having the compressor in operation. Measure the
temperature rise as close to the blower inlet and outlet as
possible.
If other than a 240V power supply is used, refer to the
BTUH CAPACITY CORRECTION FACTOR chart below.
BTUH CAPACITY CORRECTION FACTOR
SUPPLY VOLTAGE 250 230 220 208
MULTIPLICATION FACTOR 1.08 .92 .84 .75
 Five (5) heaters provide 24.0 KW at the rated
240V. Our actual measured voltage is 220V, and our
measured temperature rise is 42°F. Find the actual CFM:
 24.0KW, 42°F Rise, 240 V = 1800 CFM from the
TEMPERATURE RISE chart on the right.
Heating output at 220 V = 24.0KW x 3.413 x .84 = 68.8
MBH.
Actual CFM = 1800 x .84 Corr. Factor = 1400 CFM.

installations. The temperature rise at a particular KW
and CFM will be greater at high altitudes, while the
external static pressure at a particular CFM will be less.
CFM
3.0
kW
4.8
kW
7.2
kW
9.6
kW
14.4
kW
19.2
kW
24.0
kW
28.8
kW
600 16 25 38 51 - - - -
700 14 22 33 43 - - - -
800 12 19 29 38 57 - - -
900 11 17 26 34 51 - - -
1000 10 15 23 30 46 - - -
1100 9 14 21 27 41 55 - -
1200 8 13 19 25 38 50 - -
1300 7 12 18 23 35 46 - -
1400 7 11 16 22 32 43 54 65
1500 6 10 15 20 30 40 50 60
1600 6 9 14 19 28 38 47 57
1700 6 9 14 18 27 36 44 53
1800 5 8 13 17 25 34 42 50
1900 5 8 12 16 24 32 40 48
2000 5 8 12 15 23 30 38 45
2100 5 7 11 14 22 29 36 43
2200 4 7 11 14 21 27 34 41
2300 4 7 10 13 20 26 33 39
TEMPERATURE RISE (°F) @ 240V