Specifications

10 www.goodmanmfg.com SS-GHKR
SS-GHKR www.goodmanmfg.com 11
Product SPecificationS
Product SPecificationS
AiR HAndlER ElEctRicAl dAtA ARPf (cont.)
Air Handler
Model
Motor
Volts-Hertz-
Phase
Heater Kit
Circuit 1 Circuit 2
Amp+ HP Heater Amps MCA¹ MOP² Heater Amps MCA¹ MOP²
ARPF486016CA 4.06 3/4 208/240-60-1 ---------- 0/0 5.1/5.1 15/15 ----- ----- -----
HKR-03* 10.8/12.5 19/21 20/25 ----- ----- -----
HKR-05*/-05C* 17.2/19.8 27/30 30/30 ----- ----- -----
HKR-06* 21.7/25 32/36 35/40 ----- ----- -----
HKR-08*/-08C* 25.3/29.2 37/42 40/45 ----- ----- -----
HKR-10*/-10C* 34.3/39.6 48/55 50/60 ----- ----- -----
HKR-15C* 34.3/39.6 48/55 50/60 17.2/19.8 21/25 25/25
HKR-20C* 34.3/39.6 48/55 50/60 34.3/39.6 43/49 45/50
HKR-21C* 37.9/43.8 52/60 60/60 37.9/43.8 47/55 50/60
^HKR3-15* 0/0 5.1/5.1 15/15 31.3/36.1 39/45 40/50
^HKR3-20* 0/0 5.1/5.1 15/15 40.7/46.9 51/59 60/60
ARPF496116AA 4.3 3/4 208/240-60-1 ---------- 0/0 5.4/5.4 15/15 ----- ----- -----
HKR-03* 10.8/12.5 19/21 20/20 ----- ----- -----
HKR-05*/-05C* 17.1/19.8 27/30 30/30 ----- ----- -----
HKR-06* 21.6/25.0 32/37 40/40 ----- ----- -----
HKR-08*/-08C* 25.2/29.1 37/39 40/40 ----- ----- -----
HKR-10*/-10C* 34.3/39.6 48/55 60/60 ----- ----- -----
HKR-15C* 34.3/39.6 48/55 60/60 17.1/19.8 22/25 30/30
HKR-20C* 34.3/39.6 48/55 60/60 34.3/39.6 43/49 60/60
HKR-21C* 37.9/43.8 53/59 60/60 37.9/43.8 48/55 60/60
^HKR3-15* 0/0 5.4/5.4 15/15 31.2/36.1 39/45 60/60
^HKR3-20* 0/0 5.4/5.4 15/15 40.6/46.9 51/59 60/60
ARPF496116CA 4.06 3/4 208/240-60-1 ---------- 0/0 5.1/5.1 15/15 ----- ----- -----
HKR-03* 10.8/12.5 19/21 20/25 ----- ----- -----
HKR-05*/-05C* 17.2/19.8 27/30 30/30 ----- ----- -----
HKR-06* 21.7/25.0 32/36 35/40 ----- ----- -----
HKR-08*/-08C* 25.3/29.2 37/42 40/45 ----- ----- -----
HKR-10*/-10C* 34.3/39.6 48/55 50/60 ----- ----- -----
HKR-15C* 34.3/39.6 48/55 50/60 17.2/19.8 21/25 25/25
HKR-20C* 34.3/39.6 48/55 50/60 34.3/39.6 43/49 45/50
HKR-21C* 37.9/43.8 52/60 60/60 37.9/43.8 47/55 50/60
HKR3-15* 0/0 5.1/5.1 15/15 31.3/36.1 39/45 40/50
HKR3-20* 0/0 5.1/5.1 15/15 40.7/46.9 51/59 60/60
¹ Minimum Circuit Ampacity @ 208 / 240 V
^ Heat Kit requires three-phase power supply
C Circuit breaker opon --- indicates Not Required
² Maximum Overcurrent Protecon Device @ 208 / 240V
* Revision level that may or may not be designated
Notes
All HKR ampacies noted above include air handler motor amps, excluding three-phase models.
HKA meets the new UL1995 requirements for 15 and 20KW heaters; HKR-21C* is Obsolete; no replacement