Product SPecificationS
Product SPecificationS
AiR HAndlER ElEctRicAl dAtA ASPf
Model &
Heat Kit Usage
Circuit 1 Circuit 2 Single-Point Kit
Heater Amps MCA¹ MOP² Heater Amps MCA¹ MOP² MCA¹ MOP²
ASPF183016B* 0 / 0 3.1 / 3.1 15 / 15 --- --- --- --- ---
HKR-03* 10.8 / 12.5 17 / 19 20 / 20 --- --- --- -- --
HKR-05* / -05C* 17.1 / 19.8 27 / 30 30 / 30 --- --- --- -- --
HKR-06* 21.6 / 25.0 32 / 37 40 / 40 --- --- --- -- --
HKR-08* / -08C* 25.3 / 29.2 37 / 39 40 / 40 --- --- --- -- --
HKR-10* / -10C* 34.3 / 39.6 48 / 55 60 / 60 --- --- --- -- --
HKA-15C* 34.3 / 39.6 46 / 53 60 / 60 17.2 / 19.8 21 / 25 30 / 30 67/77 70 / 80
^HKR3-15* 0 / 0 3.1 / 3.1 15 / 15 31.2 / 36.1 39 / 45 60 / 60 -- --
ASPF183016D* 0 / 0 3.6 / 3.6 15 / 15 --- --- --- --- ---
HKR-03* 10.8 / 12.5 17 / 19 20 / 20 --- --- --- -- --
HKR-05* / -05C* 17.2 / 19.8 25 / 28 30 / 30 --- --- --- -- --
HKR-06* 21.6 / 25.0 31 / 35 35 / 35 --- --- --- -- --
HKR-08* / -08C* 25.3 / 29.2 35 / 40 40 / 45 --- --- --- -- --
HKR-10* / -10C* 34.3 / 39.6 47 / 53 50 / 60 --- --- --- -- --
HKA-15C* 34.3 / 39.6 47 / 53 50 / 60 17.2 / 19.8 21 / 25 25 / 25 68/78 70 / 80
^HKR3-15* 0 / 0 3.6 / 3.6 15 / 15 31.2 / 36.1 39 / 45 40 / 50 -- --
ASPF303616** 0 / 0 3.8 / 3.8 15 / 15 --- --- --- -- --
HKR-03* 10.8 / 12.5 15 / 17 20 / 20 --- --- --- -- --
HKR-05* / -05C* 17.1 / 19.8 24 / 27 30 / 30 --- --- --- -- --
HKR-06* 21.6 / 25.0 32 / 37 40 / 40 --- --- --- -- --
HKR-08* / -08C* 25.3 / 29.2 35 / 40 40 / 40 --- --- --- -- --
HKR-10* / -10C* 34.3 / 39.6 48 / 55 60 / 60 --- --- --- -- --
HKA-15C* 34.3 / 39.6 46 / 53 60 / 60 17.2 / 19.8 21 / 25 30 / 30 68/78 70 / 80
HKA-20C* 34.3 / 39.6 51 / 57 60 / 60 34.3 / 39.6 43 / 50 60 / 60 90/103 90 / 110
^HKR3-15* 0 / 0 3.8 / 3.8 15 / 15 31.2 / 36.1 39 / 45 60 / 60 -- --
^HKR3-20* 0 / 0 3.8 / 3.8 15 / 15 40.6 / 46.9 51 / 59 60 / 60 -- --
ASPF313716A* 0 / 0 3.8 / 3.8 15 / 15 --- --- --- --- ---
HKR-03* 10.8 / 12.5 15 / 17 20 / 20 --- --- --- --- ---
HKR-05* / -05C* 17.1 / 19.8 24 / 27 30 / 30 --- --- --- --- ---
HKR-06* 21.6 / 25.0 32 / 37 40 / 40 --- --- --- --- ---
HKR-08* / -08C* 25.3 / 29.2 35 / 40 40 / 40 --- --- --- --- ---
HKR-10* / -10C* 34.3 / 39.6 48 / 55 60 / 60 --- --- --- --- ---
HKA-15C* 34.3 / 39.6 46 / 53 60 / 60 17.2 / 19.8 21 / 25 30 / 30 68/78 70 / 80
HKA-20C* 34.3 / 39.6 51 / 57 60 / 60 34.3 / 39.6 43 / 50 60 / 60 90/103 90 / 110
^HKR3-15* 0 / 0 3.8 / 3.8 15 / 15 31.2 / 36.1 39 / 45 60 / 60 -- --
^HKR3-20* 0 / 0 3.8 / 3.8 15 / 15 40.6 / 46.9 51 / 59 60 / 60 -- --
¹ Minimum Circuit Ampacity @ 208 / 240 V
² Maximum Overcurrent Protecon Device @ 208 / 240 V
* Revision level that may or may not be designated
C Circuit breaker opon CA is for 208V and CB is for 240V
--- indicates Not Required
^ Heat Kit requires three-phase power supply
Note: All HKR ampacies noted above include air handler motor amps, excluding three-phase models.