Specifications

24 www.goodmanmfg.com SS-GHKR
SS-GHKR www.goodmanmfg.com 25
Product SPecificationS
Product SPecificationS
ElEctRicAl dAtA foR gPc13m PAcKAgEd UnitS (BloWER only, HEAt modE)
Model and
Heat Kit Usage
Circuit #1 Circuit #2 Single-Point Kit
Actual kW /
BTU@ 240V
MCA¹ MOP² MCA¹ MOP² MCA¹ MOP²
GPC1336M41**
1.9 --- --- --- -- -- ---
HKR-05*, HKR-05C*
21/25 25/25 --- --- 25 40 4.75/16,200
HKR-08*, HKR-08C*
32/36 35/40 --- --- 34/39 40/40 7.0/23,800
HKR-10*, HKR-10C*
43/49 45/50 --- --- 45/52 60/60 9.5/32,400
HKP-15C*
43/49 45/50 21/25 25/25 66/76 70/80 14.25/48,600
GPC1348M41**
7.3 --- --- --- -- -- ---
HKR-05*, HKR-05C*
21/25 25/25 --- --- 32 50 4.75/16,200
HKR-08*, HKR-08C*
32/36 35/40 --- --- 38/40 50 7.0/23,800
HKR-10*, HKR-10C*
43/49 45/50 --- --- 49/56 60/60 9.5/32,400
HKP-15C*
43/49 45/50 21/25 25/25 70/80 80/90 14.25/48,600
HKP-20C
43/49 45/50 43/49 45/50 92/105 100/110 19.0/64,800
GPC1360M41**
9.5 --- --- --- -- -- ---
HKR-05*, HKR-05C*
21/25 25/25 --- --- 42 60 4.75/16,200
HKR-08*, HKR-08C*
32/36 35/40 --- --- 42 60 7.0/23,800
HKR-10*, HKR-10C*
43/49 45/50 --- --- 51/58 60/60 9.5/32,400
HKP-15C*
43/49 45/50 21/25 25/25 72/82 80/90 14.25/48,600
HKP-20C
43/49 45/50 43/49 45/50 93/107 100/110 19.0/64,800
¹ Minimum Circuit Ampacity @ 208 / 240 V
² Maximum Overcurrent Protecon Device @ 208 / 240 V
* Revision level that may or may not be designated
C Circuit breaker opon
^ Heat Kit requires three-phase power supply
Note: HKP-15C* and HKP-20C* replace HKR-15C and HKR-20C respecvely to meet new UL1995 requirements.