Specifications

6 www.goodmanmfg.com SS-GHKR
SS-GHKR www.goodmanmfg.com 7
Product SPecificationS
Product SPecificationS
AiR HAndlER ElEctRicAl dAtA ARPf
Air Handler
Model
Motor
Volts-Hertz-
Phase
Heater Kit
Circuit 1 Circuit 2
Amp+ HP Heater Amps MCA¹ MOP² Heater Amps MCA¹ MOP²
ARPF182416AA 1.7 1/3 208/240-60-1 ---------- 0/0 2.1/2.1 15/15 ----- ----- -----
ARPF182416BA HKR-03* 10.8/12.5 16/18 20/20 ----- ----- -----
HKR-05*/-05C* 17.1/19.8 24/27 30/30 ----- ----- -----
HKR-06* 21.6/25.0 30/34 40/40 ----- ----- -----
HKR-08*/-08C* 25.2/29.1 34/39 40/40 ----- ----- -----
HKR-10*/-10C* 34.3/39.6 45/52 60/60 ----- ----- -----
HKR-15C* 34.3/39.6 45/52 60/60 17.1/19.8 22/25 30/30
ARPF182416CA 1.9 1/3 208/240-60-1 ---------- 0/0 2.4/2.4 15/15 ----- ----- -----
HKR-03* 10.8/12.5 16/18 20/20 ----- ----- -----
HKR-05*/-05C* 17.2/19.8 24/27 25/30 ----- ----- -----
HKR-06* 21.7/25.0 29/34 30/35 ----- ----- -----
HKR-08*/-08C* 25.3/29.2 34/39 35/40 ----- ----- -----
HKR-10*/-10C* 34.3/39.6 45/52 50/60 ----- ----- -----
HKR-15C* 34.3/39.6 45/52 50/60 17.2/19.8 21/25 25/25
ARPF193116AA 1.48 1/4 208/240-60-1 ---------- 0/0 1.9/1.9 15/15 ----- ----- -----
ARPF193116BA HKR-03* 10.8/12.5 15/17 20/20 ----- ----- -----
HKR-05*/-05C* 17.1/19.8 23/27 30/30 ----- ----- -----
HKR-06* 21.6/25.0 29/33 40/40 ----- ----- -----
HKR-08*/-08C* 25.2/29.1 33/38 40/40 ----- ----- -----
HKR-10*/-10C* 34.3/39.6 45/51 60/60 ----- ----- -----
HKR-15C* 34.3/39.6 45/51 60/60 17.1/19.8 22/25 30/30
ARPF193116CA 1.48 1/4 208/240-60-1 ---------- 0/0 1.9/1.9 15/15 ----- ----- -----
HKR-03* 10.8/12.5 15/17 20/20 ----- ----- -----
HKR-05*/-05C* 17.2/19.8 23/27 25/30 ----- ----- -----
HKR-06* 21.7/25.0 29/33 30/35 ----- ----- -----
HKR-08*/-08C* 25.3/29.2 33/38 35/40 ----- ----- -----
HKR-10*/-10C* 34.3/39.6 45/51 45/60 ----- ----- -----
HKR-15C* 34.3/39.6 45/51 45/60 17.2/19.8 21/25 25/25
ARPF303016AA 2.64 1/3 208/240-60-1 ---------- 0/0 3.3/3.3 15/15 ----- ----- -----
ARPF303016BA HKR-03* 10.8/12.5 17/19 20/20 ----- ----- -----
HKR-05*/-05C* 17.1/19.8 25/28 30/30 ----- ----- -----
HKR-06* 21.6/25.0 30/35 40/40 ----- ----- -----
HKR-08*/-08C* 25.2/29.1 35/40 40/40 ----- ----- -----
HKR-10*/-10C* 34.3/39.6 46/53 60/60 ----- ----- -----
HKR-15C* 34.3/39.6 46/53 60/60 17.1/19.8 22/25 30/30
HKR-20C* 34.3/39.6 46/53 60/60 34.3/39.6 43/49 60/60
HKR-21C* 37.9/43.8 51/58 60/60 37.9/43.8 48/55 60/60
^HKR3-15* 0/0 3.3/3.3 15/15 31.2/36.1 39/45 60/60
^HKR3-20* 0/0 3.3/3.3 15/15 40.6/46.9 51/59 60/60
¹ Minimum Circuit Ampacity @ 208 / 240 V
^ Heat Kit requires three-phase power supply
C Circuit breaker opon --- indicates Not Required
² Maximum Overcurrent Protecon Device @ 208 / 240V
* Revision level that may or may not be designated
Notes
All HKR ampacies noted above include air handler motor amps, excluding three-phase models.
HKA meets the new UL1995 requirements for 15 and 20KW heaters; HKR-21C* is Obsolete; no replacement