HKR & HKS Spec Sheet

20 www.goodmanmfg.com SS-GHKR
SS-GHKR www.goodmanmfg.com 21
Product SPecificationS
Product SPecificationS
ElEctRicAl dAtA foR gPH15m PAcKAgEd UnitS (BloWER only, HEAt modE)
Model and
Heat Kit Usage
Circuit #1 Circuit #2 Single-Point Kit
Actual kW /
BTU@ 240V
MCA¹ MOP² MCA¹ MOP² MCA¹ MOP²
APH1524M41A* 5.4 --- --- --- -- -- ---
HKR-05*, HKR-05C* 21 / 25 25 / 25 --- --- 46 50 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 58 60 7.0 / 23,800
HKR-10*, HKR-10C* 43 / 49 45 / 50 --- --- 71 80 9.5 / 32,400
APH1530M41A* 5.4 --- --- --- -- -- ---
HKR-05*, HKR-05C* 21 / 25 25 / 25 --- --- 48 50 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 60 60 7.0 / 23,800
HKR-10*, HKR-10C* 43 / 49 45 / 50 --- --- 73 80 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 97 100 14.25 / 48,600
APH1536M41A* 5.4 --- --- --- -- -- ---
HKR-05*, HKR-05C* 21 / 25 25 / 25 --- --- 51 60 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 63 70 7.0 / 23,800
HKR-10*, HKR-10C* 43 / 49 45 / 50 --- --- 76 80 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 101 110 14.25 / 48,600
APH1543M41A* 3.6 --- --- --- -- -- ---
HKR-05*, HKR-05C* 21 / 25 25 / 25 --- --- 51 60 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 63 70 7.0 / 23,800
HKR-10*, HKR-10C* 43 / 49 45 / 50 --- --- 76 80 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 101 110 14.25 / 48,600
APH1549M41A* 3.6 --- --- --- -- -- ---
HKR-05*, HKR-05C* 21 / 25 25 / 25 --- --- 56 70 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 67 80 7.00 / 23,800
HKR-10*, HKR-10C* 43 / 49 45 / 50 --- --- 80 90 9.50 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 105 110 14.25 / 48,600
HKP-20C* 43 / 49 45 / 50 43 / 49 45 / 50 132 150 19.0 / 64,800
APH1560M41A* 8.8 --- --- --- -- -- ---
HKR-05*, HKR-05C* 21 / 25 25 / 25 --- --- 67 80 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 79 90 7.0 / 23,800
HKR-10*, HKR-10C* 43 / 49 45 / 50 --- --- 92 100 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 116 125 14.25 / 48,600
HKP-20C* 43 / 49 45 / 50 43 / 49 45 / 50 144 150 19.0 / 64,800
¹ Minimum Circuit Ampacity @ 208 / 240 V
² Maximum Overcurrent Protecon Device @ 208 / 240 V
* Revision level that may or may not be designated
C Circuit breaker opon
^ Heat Kit requires three-phase power supply
Note: HKP-15C* and HKP-20C* replace HKR-15C and HKR-20C respecvely to meet new UL1995 requirements.