HKR & HKS Spec Sheet

22 www.goodmanmfg.com SS-GHKR
SS-GHKR www.goodmanmfg.com 23
Product SPecificationS
Product SPecificationS
ElEctRicAl dAtA foR gPH13m PAcKAgEd UnitS (BloWER only, HEAt modE)
Model and
Heat Kit Usage
Circuit #1 Circuit #2 Single-Point Kit
Actual kW /
BTU@ 240V
MCA¹ MOP² MCA¹ MOP² MCA¹ MOP²
GPH1324M41** 1.9 --- --- --- -- -- ---
HKR-05*, HKR-05C* 21 / 25 25 / 25 --- --- 44 50 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 55 60 7.0 / 23,800
HKR-10*, HKR-10C* 43 / 49 45 / 50 --- --- 68 70 9.5 / 32,400
GPH1330M41** 1.9 --- --- --- -- -- ---
HKR-05*, HKR-05C* 21 / 25 25 / 25 --- --- 48 50 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 59 60 7.0 / 23,800
HKR-10*, HKR-10C* 43 / 49 45 / 50 --- --- 72 80 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 97 100 14.25 / 48,600
GPH1336M41** 1.9 --- --- --- -- -- ---
HKR-05*, HKR-05C* 21 / 25 25 / 25 --- --- 50 60 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 62 70 7.0 / 23,800
HKR-10*, HKR-10C* 43 / 49 45 / 50 --- --- 75 80 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 100 100 14.25 / 48,600
GPH1342M41** 3.6 --- --- --- -- -- ---
HKR-05*, HKR-05C* 21 / 25 25 / 25 --- --- 52 60 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 63 70 7.0 / 23,800
HKR-10*, HKR-10C* 43 / 49 45 / 50 --- --- 76 80 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 101 110 14.25 / 48,600
GPH1348M41** 7.3 --- --- --- -- -- ---
HKR-05*, HKR-05C* 21 / 25 25 / 25 --- --- 59 70 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 71 80 7.0 / 23,800
HKR-10*, HKR-10C* 43 / 49 45 / 50 --- --- 84 90 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 109 110 14.25 / 48,600
HKP-20C* 43 / 49 45 / 50 43 / 49 45 / 50 136 150 19.0 / 64,800
GPH1360M41** 9.5 --- --- --- -- -- ---
HKR-05*, HKR-05C* 21 / 25 25 / 25 --- --- 67 80 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 78 90 7.0 / 23,800
HKR-10*, HKR-10C* 43 / 49 45 / 50 --- --- 91 100 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 116 125 14.25 / 48,600
HKP-20C* 43 / 49 45 / 50 43 / 49 45 / 50 144 150 19.0 / 64,800
¹ Minimum Circuit Ampacity @ 208 / 240 V
² Maximum Overcurrent Protecon Device @ 208 / 240 V
* Revision level that may or may not be designated
C Circuit breaker opon
^ Heat Kit requires three-phase power supply
Note: HKP-15C* and HKP-20C* replace HKR-15C and HKR-20C respecvely to meet new UL1995 requirements.