Heating kW Correction Factor
Supply Voltage 240 230 220 210 208
Correction Factor 1.00 0.92 0.84 0.77 0.75
Mul
Air Handler Electrical Data AVPTC (cont.)

  
       
HKSC05XC - 240 V
Breaker
20 34 35 --- --- --- --- ---
HKSC08XC - 240 V 33.3 50.3 60 --- --- --- --- ---
HKSC10XC - 240 V 40 58.6 60 --- --- --- --- ---
HKSC15XB - 240 V 40 58.6 60 20 25 25 83.6 90
HKSC20DB - 240 V 40 58.6 60 40 50 50 108.6 110
HKSC15XF - 240 V ^ 0 8.6 15 34.6 43 45 --- ---
HKSC20XF - 240 V ^ 0 8.6 15 43 54 60 --- ---
HKSC25DB - 240 V 60 84 90 40 50 50 133.6 150
¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25
² Maximum Overcurrent Protecon = 2.25 X Motor Amps + Heater Amps
^ Circuit 1: Single-phase for Air Handlers Circuit 2: Three-phase for HKR3 Heater Kits
Note: The 208 or 240 in the heat kit part number eld is for claricaon of the nominal voltage for this model.