Air Handler Electrical Data ARUF (cont.)

  
       
HKSC05XC - 240 V
Breaker
20 31 35 --- --- --- --- ---
HKSC08XC - 240 V
33.3 47 50 --- --- --- --- ---
HKSC10XC - 240 V
40 56 60 --- --- --- --- ---
HKSC15XB - 240 V
40 56 60 20 25 25 81 90
HKSC20DB - 240 V
40 56 60 40 50 50 106 110
HKSC15XF - 240 V ^
0 6 15 34.6 43 45 --- ---
HKSC20XF - 240 V ^
0 6 15 43 54 60 --- ---
HKSC25DB - 240 V
60 81 90 40 50 50 131 150
Heating kW Correction Factor
 240 230 220 210 208
 1.00 0.92 0.84 0.77 0.75
Multiply the 240-volt heating capacity by correction factors.
¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25
² Maximum Overcurrent Protection = 2.25 X Motor Amps + Heater Amps
--- indicates Not Required
Note : The 208 or 240 in the heat kit part number eld is for clarication of the nominal voltage for this model.
^ Three Phase
3
Notation is correct as XB because technically the 240V heater kit application can be used here without any issues.