HKS Spec Sheet

32 www.goodmanmfg.com SS-GHKR
SS-GHKR www.goodmanmfg.com 33
Air Handler Electrical Data MBVC

  
       
MBVC1200AA-1A*
HKR-03*
HKR-05* / 05C*
HKR-06*
HKR-08* / -08C*
HKR-10* / -10C*
HKA-15C*
0 / 0
10.8 / 12.5
17.2 / 19.8
21.7 / 25.0
25.3 / 29.2
34.3 / 39.6
34.3 / 39.6
4.9 / 4.9
18 / 20.5
26 / 29.6
32 / 36.1
36.5 / 41
47.8 / 54
47.8 / 54
15 / 15
20 / 25
30 / 30
35 / 40
40 / 45
50 / 60
50 / 60
---
---
---
---
---
---
17.2 / 19.8
---
---
---
---
---
---
21.4 / 24.7
---
---
---
---
---
---
25 / 25
---
---
---
---
---
---
69/79
---
---
---
---
---
---
70 / 80
MBVC1600AA-1A*
HKR-03*
HKR-05* / 05C*
HKR-06*
HKR-08* / -08C*
HKR-10* / -10C*
HKA-15C*
0 / 0
10.8 / 12.5
17.2 / 19.8
21.7 / 25.0
25.3 / 29.2
34.3 / 39.6
34.3 / 39.6
6.5 / 6.5
20.1 / 22
27.9 / 31
34 / 37.8
38.1 / 43
49.4 / 56
49.4 / 56
15 / 15
25 / 25
30 / 35
35 / 40
40 / 45
50 / 60
50 / 60
---
---
---
---
---
---
17.2 / 19.8
---
---
---
---
---
---
21.4 / 24.7
---
---
---
---
---
---
25 / 25
---
---
---
---
---
---
71/81
---
---
---
---
---
---
80 / 90
MBVC2000AA-1A*
HKR-03*
HKR-05* / 05C*
HKR-06*
HKR-08* / -08C*
HKR-10* / -10C*
HKA-15C*
HKA-20C*
0 / 0
10.8 / 12.5
17.2 / 19.8
21.7 / 25.0
25.3 / 29.2
34.3 / 39.6
34.3 / 39.6
34.3 / 39.6
6.5 / 6.5
20.1 / 22
27.9 / 31
34 / 37.8
38.1 / 43
49.4 / 56
49.4 / 56
49.4 / 56
15 / 15
25 / 25
30 / 35
35 / 40
40 / 45
50 / 60
50 / 60
50 / 60
---
---
---
---
---
---
17.2 / 19.8
34.3 / 39.6
---
---
---
---
---
---
21.4 / 24.7
42.9 / 49.5
---
---
---
---
---
---
25 / 25
45 / 50
---
---
---
---
---
---
70/80
92/105
---
---
---
---
---
---
70 / 80
100 / 110
All ampacies noted above include air handler motor amps
Circuit 1: Single-phase for Air Handlers / Circuit 2: Three-phase for HKR3 Heater
Kits
¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25
² Maximum Overcurrent Protecon = 2.25 X Motor Amps + Heater Amps
* Revision level that may or may not be designated
C = Circuit Breaker Opon
--- indicates Not Required
Only applicable when HKA kits are included in table
HKA meets the new UL1995 requirements for 15 and 20KW heaters
MBVC and MBR models
Heating kW Correction Factor
 240 230 220 210 208
 1.00 0.92 0.84 0.77 0.75
Mulply the 240-volt heang capacity by correcon factors.