Kit Instructions
LPM-08
TWO-STAGE FURNACE, NATURAL GAS TO LP GAS CONVERSION KIT
INSTALLATION INSTRUCTIONS
ATTENTION INSTALLING PERSONNEL
As a professional installer, you have an obligation to know
the product better than the customer. This includes all safety
precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with
this Instruction Manual. Pay special attention to all safety
warnings. Often during installation or repair, it is possible to
place yourself in a position which is more hazardous than
when the unit is in operation.
Remember, it is your responsibility to install the product safely
and to know it well enough to be able to instruct a customer
in its safe use.
Safety is a matter of common sense...a matter of thinking
before acting. Most dealers have a list of specifi c good safety
practices...follow them.
The precautions listed in this Installation Manual are intended
as supplemental to existing practices. However, if there is a
direct confl ict between existing practices and the content of
this manual, the precautions listed here take precedence.
IO-818A
02/2015
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION
DESCRIPTION
This natural gas to L.P. (liquid petroleum) gas conversion
kit allows White-Rodgers gas valve 36G54 (0151F00000P),
36J54 (0151M00027) or Honeywell VR9205Q (0151M00014
/ 0151M00028) to be used on L.P. gas applications.
Use the following parts list to ensure that all parts listed below
are present and in an undamaged condition. IF ANY DOUBT
EXISTS ABOUT THE CONDITIONS OF ANY COMPONENT
WITHIN THIS KIT, DO NOT USE THIS KIT AND CONTACT
YOUR SUPPLIER FOR A NEW KIT.
PARTS LIST
Part
Number
Description Quantity
0163F00000P White-Rodgers LP Conversion Kit F92-1008 1
0163M00139 Honeywell LP Conversion Kit 50033841 1
B14933151 Conversion Label 1
B40899125 1.25mm Spud Orifi ce Assembly 1
IO-818* LPM-08 Installation Instructions 1
0151K00000S 36G54 Pressure Check Kit Valve 1
With the exception of the natural gas burner orifi ces, all of
the fasteners and other components removed to perform
this conversion are to be reused. Any component found to
be damaged due to this conversion must be replaced with
factory authorized replacement parts before this furnace can
be put into operation.
This furnace is equipped for two-stage heating operation.
The gas valve manifold pressure must be set with fi rst stage
operating at 6” +/-0.3” W.C. manifold pressure and the second
stage must be set at 10” +/-0.3” W.C. manifold pressure. The
accuracy of these pressures must be checked as shown in
steps 25 and 26 of these instructions.
The gas valve is equipped with a 3-pin polarized plug which
prevents this wiring from being installed incorrectly.
CAUTION
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING
CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS
OPERATION. VERIFY PROPER OPERATION AFTER SERVICING.
NOTE: Do not use power tools for any adjustments on
gas valves.