Datasheet

A-BP
Series
www.goodwe.com
Technical Data
GW5000A-BP GW6000A-BP GW7000A-BP GW7600A-BP GW8600A-BP GW9600A-BP
Battery Input Data
Battery Type Li-Ion Li-Ion Li-Ion Li-Ion Li-Ion Li-Ion
Battery Voltage Range (V)
*1
80~495 80~495 80~495 80~495 80~495 80~495
Max. Continuous Charging Current (A) 50 50 50 50 50 50
Max. Continuous Discharging Current (A) 50 50 50 50 50 50
AC Output Data (On-grid)
Max. Apparent Power Output to Utility Grid (VA)
5000 6000 7000 7600 8600 9600
Max. Apparent Power from Utility Grid (VA)
6000 7200 8400 9120 9600 9600
Output Voltage Range ((Vac))
211 to 264 @240 211 to 264 @240 211 to 264 @240 211 to 264 @240 211 to 264 @240 211 to 264 @240
Nominal AC Grid Frequency (Hz) 60 60 60 60 60 60
Max. AC Current Output to Utility Grid (A) 20.8 25 29.2 31.7 35.8 40
Max. AC Current From Utility Grid (A) 25 30 35 38 40 40
Power Factor ~1 (Adjustable from 0.8 leading to 0.8 lagging)
Max. Total Harmonic Distortion <3% <3% <3% <3% <3% <3%
AC Output Data (Back-up)
Max. Output Apparent Power@240V (VA)
5000 (6000@60sec) 6000 (7200@60sec) 7000 (8400@60sec) 7600 (9120@60sec)
8600 (10320@60sec) 9600 (11520@60sec)
Max. Output Current @240V (A) 20.8 25 29.2 31.7 35.8 40
Nominal Output Voltage L1-L2/L-N (Vac) 240/120 240/120 240/120 240/120 240/120 240/120
Nominal Output Frequency (Hz) 60 60 60 60 60 60
Output THDv (@Linear Load)
<3% <3% <3% <3% <3% <3%
Efciency
Max. Battery to AC Efficiency 96.6% 96.6% 96.6% 96.6% 96.6% 96.6%
Protection
PV Insulation Resistance Detection Integrated Integrated Integrated Integrated Integrated Integrated
Residual Current Monitoring Integrated Integrated Integrated Integrated Integrated Integrated
Battery Reverse Polarity Protection Integrated Integrated Integrated Integrated Integrated Integrated
Anti-islanding Protection Integrated Integrated Integrated Integrated Integrated Integrated
AC Overcurrent Protection Integrated Integrated Integrated Integrated Integrated Integrated
AC Short Circuit Protection Integrated Integrated Integrated Integrated Integrated Integrated
AC Overvoltage Protection Integrated Integrated Integrated Integrated Integrated Integrated
General Data
Operating Temperature Range (°F) -31°F~140°F (-35°C~60°C)
Relative Humidity 0~95% 0~95% 0~95% 0~95% 0~95% 0~95%
Max. Operating Altitude (ft)
13123ft (4000m)
13123ft (4000m)
13123ft (4000m)
13123ft (4000m)
13123ft (4000m)
13123ft (4000m)
Cooling Method Intelligent Fan Intelligent Fan Intelligent Fan Intelligent Fan Intelligent Fan Intelligent Fan
Display LED & APP(WiFi, Bluetooth)
Communication with BMS RS485; CAN RS485; CAN RS485; CAN RS485; CAN RS485; CAN RS485; CAN
Communication with Meter RS485 RS485 RS485 RS485 RS485 RS485
Communication with Portal Wi-Fi; LAN(Optional)
Weight (lb) 62.8lb (28.5kg) 62.8lb (28.5kg) 70.5lb (32kg) 70.5lb (32kg) 70.5lb (32kg) 70.5lb (32kg)
Dimension W×H×D (inch) 16.3in × 33.1in × 6.9in (415mm × 841mm × 175mm)
Noise Emission (dB) <45 <45 <45 <45 <45 <45
Topology Transformerless
Self-consumption at Night (W)
*2
<20 <20 <20 <20 <20 <20
Ingress Protection Rating NEMA Type 4X NEMA Type 4X NEMA Type 4X NEMA Type 4X NEMA Type 4X NEMA Type 4X
Mounting Method Wall Bracket Wall Bracket Wall Bracket Wall Bracket Wall Bracket Wall Bracket
Certication
Grid Standards UL1741 SA, California Rule 21, HECO Rule 14, IEEE 1547, IEEE 1547.1
Safety Regulation UL 1741, CSA 22.2 No. 107-01, UL 1998, UL991, UL1699B
EMC FCC part15 CLASS B
*1: Battery discharge/charge power limited by voltage. When A-BP is in microgrid application, the maximum battery voltage is 405V.
*2: No Back-up Output.
*: Peak output apparent power@240V can be reached only if battery power is enough.
*: Please visit GoodWe website for the latest certificates.
GoodWe-Single page-20220307-EN-V2.0. Information may be subject to change without notice during product improving.