SECU-A5.4L
LiFePO
4
49kg
400x226.2x484.2mm
IP20 (indoor)
5.4 kWh
4.8 kWh
90%
51.2 V
48 ~ 57.6 V
≤ 20 mΩ
50 A
50 A
-10 °C ~ 50 °C [1]
15% ~ 85%
6 Parallels
5.4/10.8/16.2/21.6/27/32.4 kWh
4.8/9.6/14.4/19.2/24/28.8 kWh
50A (1 Module) / 100A (2~6 Modules)
50A (1 Module) / 100A (2~6 Modules)
system voltage, current, cell voltage, cell temperature,
PCBA temperature
CAN
CE, UN38.3
7. Battery Parameters
Physical Parameters
Electrical Parameters
System Configuration
[1] When the temperature is below zero, the battery are not allowed to charge. When above 40℃,
the power output decreased.
Technical Data SECU A5.4-20
2*SECU A5.4-20
3*SECU A5.4-20
Nominal Dis-/Charge
Current (A)*2
Operating Voltage
Range (V)
Nominal Voltage (V)
Nominal Power (kW)*2
Short-Circuit Current
Relative Humidity
Communication
Weight (kg)
Ingress Protection Rating
Storage Temperature (℃)
Mounting Method
Round-trip Efficiency
Cycle Life*3
Safety
EMC
Transportation
Standard
and
Certification
Dimensions (W×H×D mm)
Max. Operating Altitude
(m)
Operating Temperature
Range (℃)
Cell Configuration
Cell Type
Number of Module
5.4
1
16S1P 16S2P 16S3P
2 3
10.8
SECU A5.4-20
LFP( LiFePO4)
51.2
47.5~57.6
50
100
2.56
0~95%
2000
49 98 147
CAN、 RS485
403x227x455 (SECU A5.4-20)
IP 20
95.0%
≥ 4000 @0.5C/0.5C
CE, RCM
UN38.3
-20 ~ +40 (≤One Month) / 0 ~ +35 (≤One Year)
Grounded/ Cabinet
5.12
2.323kA@1.0ms
Charge: 0 ~ +50 / Discharge: -10 ~ +50
16.2
Battery Module
Usable Energy (kWh)*1
*1: Test conditions, 100% DOD, 0.2C charge & discharge at +25±2 °C for battery system
at beginning life. System Usable Energy may vary with different Inverter.
*2: Nominal Dis-/Charge Current and power derating will occur related to Temperature and
SOC.
*3: Based on Cell under 0.5C/0.5C @ 25±2℃ test condition and 80% EOL.
IEC62619, IEC63056,CEC