5.Fire Fighting Measures
5.1 Risk Analysis (electrical shock, fire, explode, population)
There was no electrical shock risk for single cell, or battery module which voltage was less than
50V DC (the safety voltage). But if the pack had the voltage was bigger than 50V DC, the electrical
shock shall be protected.
During the shipment or testing process for LIB Pack or Module, there was danger factors like drop,
crush, broken, metal short circuit, liquid immersion, the factors would lead the risk like electrical
shock, catch fire. If pack was in well sealed box, there was gas explode risk; if the pack was in big
room or fans, there was not explode risk. The released liquid was the environment population risk.
5.2 Material prepare & people training
1) Water based sprayer fire extinguish: 1 set of 9L or 2 sets of 6L water spray fire extinguishers
per each 500KWh LIB pack or Modules. Or you could use portable electrical water sprayer
or hang type water spray fire extinguisher (photo 1) . The water based spray fire extinguisher
could be used for fire type ABCE = solid (A), flash point >60℃ liquid (B), gas (C), <36Kv
electrical (E) fire. It was recommended to prepare water based sprayers in the trucks.
2) Water protection sets: raincoat, galoshes, rubber gloves. Plastic rollers. Rags.
3) PPE: breathing mask, safety glass, face mask, gloves for high temperature.
4) Smoke escape: fans in wall one per 20m or portable fans in rooms. Keep gas exchange hole in
trucks.
5) Gas explode tools: open condition for devices & rooms. Some devices like high or low
temperature ovens must be sealed, there was one copper film with the diameter 200mm &
thickness 8um as the safety vent. The wall should have one fan per 20m, ≥5000m
3
per hour for
flow rate.
6) Neutralized material: prepare 10kg Ca(OH)
2
powder per 500KWh LIB pack or modules, it
was used for neutralized for release electrolyte. Because electrolyte met with water, 8% HF
would be created.
7) Voltage measure. Multimeter. Please physical block the current measure function, the mistake
would lead instrument exploding.