User Manual

21
Operating Instructions
Programmable multi-transducer SINEAX M 563
1. Read first and then …
The proper and safe operation of the device
assumes that the Operating Instructions are
read and the safety warnings given in the
sections
3. Mounting
4. Electrical connections
5. Commissioning
10. Safety notes
are observed.
The device should only be handled by appropriately
trained personal who are familiar with it and authorized to
work in electrical installations.
Contents
1. Read first and then... ................................................ 21
2. Brief description ........................................................ 21
3. Mounting ................................................................... 21
4. Electrical connections ............................................... 21
5. Commissioning.......................................................... 25
5.1 Technical data ..................................................... 25
5.2 Programming the transducer .............................. 28
6. Reconfiguring the analogue outputs ......................... 28
7. Notes of maintenance ............................................... 29
8. Releasing the transducer .......................................... 29
9. Dimensional drawing ................................................. 29
10. Safety notes .............................................................. 29
11. Instrument admission ................................................ 29
2. Brief description
SINEAX M 563 is a programmable transducer with a
RS 232 C interface. It supervises any 3 variables of an
electrical power system simultaneously and generated
3 electrically insulated analogue output signals.
The transducers are also equipped with an RS 232 serial
interface to which a PC with the corresponding software can
be connected for programming or accessing and.
The usual methods of connection, the types of measured
variables, their ratings, the transfer characteristic for each
output etc. are the main parameters that can be programmed.
The ancillary functions include displaying, recording and
evaluation of measurements on a PC, the simulation of the
outputs for test purposes and a facility for printing nameplates.
English
3. Mounting
The transducer SINEAX M 563 can be mounted on a top-hat
rail.
Note “Environmental conditions” in Section
“5.1 Technical data” when determining the place
of installation!
Simply clip the device onto the top-hat rail (EN 50 022) (see
Fig. 1).
Fig. 1. Mounting on top-hat rail 35 × 15 or 35 × 7.5 mm.
Make sure that all cables are not live when
making the connections!
Impending danger by high input voltage or
high power supply voltage!
R
ext
min. [k]
4. Electrical connections
Connect the electric conductors acc. to the instructions on
type label. Note, that the direction of energy and the phase
sequence are adhered to.
Note that, …
the data required to carry out the prescribed
measurement must correspond to those
marked on the nameplate of the SINEAX M 563
( measuring input, measuring output
and power supply, see Fig. 2)!
the resistance in the output circuit may not
overrange the current output value
15 V
I
AN
[mA]
(I
AN
= current output value)
and not underrange the voltage output value
U
AN
[V]
1 mA
(U
AN
= voltage output value)!
the measurement output cables should be
twisted pairs and run as far as possible away
from heavy current cables!
In all other respects, observe all local regulations
when selecting the type of electrical cable and
installing them!
R
ext
max. [k]