Ambient conditions
Nominal range of use
for temperature: 0…15…30…45 °C (usage group II)
Operating temperature: 10 to + 55 °C
Storage temperature: 40 to + 85 °C
Annual mean
relative humidity: 75%
5.2 Programming the transducer
The transducers SINEAX M 563 have an integrated
RS 232 C interface (SCI).
The existing programmation can be matched conveniently to
a changed situation and stored via the “Configuration software
for M 560” (Order number 146 557).
For this purpose, the RS 232 output of the transducer must
be connected to a PC via the RS 232 C (SCI) programming
cable (Order number 142 000) and the transducer must be
supplied with power supply.
The configuration software has an easy-to-operate, clear
menu structure which allows for the following functions to be
performed:
Reading and displaying the programmed configuration of
the transducer
Clear presentation of the input and output parameters
Transmission of changed programmation data to the
transducer and for archiving of a file
Protection against unauthorized change of the pro-
grammation by entry of a password
Configuration of all the usual methods of connection
(types of power system)
Fig. 5. Presentation of all programmation parameters in the main
menu.
Easy change of input and output parameters
WARNING: Watch for maximum input voltage on
transducers with internal power supply connection from
measuring input:
Power supply Power supply Maximum input
connection voltage across the
power supply
24 - 60 V AC 69 V AC
85 - 230 V AC 264 V AC
Selection possible for frequency measurement via voltage
or current
Possibility to reset the slave pointer of the output quantity
involved
Parameter setting of outputs A to C (input of measured
quantity, upper limits, limitation of upper limits and
response time per output, possible up to max. 30 s)
Graphics display of the set system behaviour of each
output
Fig. 6. Displaying, recording and evaluation of measurements.
Provision is also made for the following ancillary functions:
Displaying, recording and evaluation of measurements on
a PC
The simulation of the outputs for test purposes
Printing of nameplates
6. Reconfiguring the analogue outputs
The alternative configurations for the analogue outputs can
be seen from Table 1.
Table 1:
Action Procedure
Change the current full- Reconfigure the software,
scale value from, for but do not change the
example, 20 mA to 10 mA hardware setting.
(a hardware setting always Accuracy is reduced.
has to be made when
changing from a lower to
a higher value)
English
Programming connector on transducer
The programming connector on the transducer is connected
by the programming cable PRKAB 560 to the RS-232 interface
on the PC. The electrical insulation between the two is
provided by the programming cable.
Internal from
measuring