Datasheet

3-349-693-03
4/6.13
GMC-I Messtechnik GmbH
METRALINE RCD
CHECK
RCD Test Instrument
Touch voltage
Time to trip
Tripping current
Features
Digital display, backlit color OLED display
LED for measurement point illumination
Patented means of securing the test probes
Compact and rugged – for service calls and laboratory use
Applicable Regulations and Standards
Characteristic Values
Residual Current Devices (RCD) – General Specifications
Nom. residual current 10, 30, 100, 300, 500 mA
Deviation from nominal
residual current (-0/+0.1) I; I= I
N
, 2x I
N
, 5x I
N
Waveform of nominal
residual current Sinusoidal (AC), pulsating DC (A)
RCD type Standard and selective S
Initial polarity of
residual current 0° or 180°
Voltage range + 190 V to 255 V / 45 to 65 Hz
Residual Current Generated by the Tester (TRMS value at 20 ms):
Touch Voltage Uc and Uci
Nominal range per EN 61557-6: 3.0 to 49.0 V for a touch voltage
limit value of 25 V
Nominal range per EN 61557-6: 3.0 to 99.0 V for a touch voltage
limit value of 50 V
IEC 61010-1/-031
DIN EN 61010-1/-031
VDE 0411-1/-031
Safety requirements for electrical equipment for mea-
surement, control and laboratory use
Part 1: General requirements
Part 31: Safety requirements for hand-held probe as-
semblies for electrical measurement and test
IEC 61557-1/-6
DIN EN 61557-1/-6
VDE 0413-1/-6
Electrical safety in low voltage distribution systems up to
1000 V AC and 1500 V DC – Equipment for testing,
measuring or monitoring of protective measures
Part 1: General requirements
Part 6: Effectiveness of residual current devices
(RCD) in TT, TN and IT systems
(IEC 61557-6:2007)
IEC 61326-1
DIN EN 61326-1
Electrical equipment for measurement, control and
laboratory use – EMC requirements –
Part 1: General requirements
DIN EN 60529
VDE 0470-1
Degrees of protection provided by enclosures (IP code)
½ I
N
I
N
2 x I
N
5 x I
N
I
IN
(mA)
AC A AC A AC A AC A AC A
10 5 3.5 10 20 20 40 50 100
✓✓
30 15 10.5 30 42 60 84 150 212 ✓✓
100 50 35 100 141 200 282 500 ✓✓
300 150 105 300 424 ✓✓
500 250 175 500
Measuring Range Resolution Intrinsic Uncertainty Measuring Uncertainty
0.0 to 9.9 V
0.1 V
-0/+10%) rdg. +2 D -0/+10%) rdg. +3 D
10.0 ... 99.9 V -0/+10% rdg. -0/+10%) rdg. +1 D
Testing of residual current devices (RCDs)
Measurement of touch voltage without tripping the RCCB.
Contact voltage is measured with reference to nominal residual current using
1
/
3
of the nominal residual current value.
Tripping test with nom. residual current, time to trip measurement
Special tests for equipment and RCDs
Testing of equipment and RCDs with rising residual current including indica-
tion of tripping current
Testing of RCDs, I
N = 10, 30, 100, 300 and 500 mA
Testing RCDs with ½ • I
N, 1 • I
N, 2 • I
N,
(5 • I
N up 100 mA nominal current)
Testing RCDs with half-waves (pulsating direct current) for determining time
to trip and tripping current
Testing of special RCDs
selective , type AC, type A
Measurement of line voltage and fault loop impedance
S

Summary of content (2 pages)