Instructions
GMC-I Messtechnik GmbH 33
10.3
Earthing Resistance, Mains Powered – 2-Pole Measurement with 2-Pole Adapter or Country-Specific Plug (Schuko) without Probe
Key
R
B
Operational earth
R
E
Earthing resistance
R
i
Internal resistance
R
X
Earthing resistance through equipotential bonding 
systems
R
S
Probe resistance
PAS Equipotential bonding busbar
RE Overall earthing resistance (R
E1
//R
E2
//water pipe)
In the event that it is impossible to set a probe, earthing resis-
tance can be estimated by means of an “earth loop resistance 
measurement” without probe.
The measurement is performed exactly as described in section 10.4, 
“Earthing Resistance Measurement, Mains Powered – 3-Pole Mea-
surement: 2-Pole Adapter with Probe”, beginning on page 34. How-
ever, no probe is connected to the probe connector socket (17).
The resistance value R
ELoop
 obtained with this measuring method 
also includes operational earth electrode resistance R
B
 and resis-
tance at phase conductor L. These values must be deducted from 
the measured value in order to determine earthing resistance.
If conductors of equal cross section are assumed (phase conductor L 
and neutral conductor N), phase conductor resistance is half as great 
as supply impedance Z
L-N
 (phase conductor + neutral conductor). 
Supply impedance can be measured as described in section 9 
beginning of page 29. In accordance with DIN VDE 0100, operational 
earth electrode R
B
 must lie within a range of “0
Ω
 to 2
Ω
”.
1) Measurement:  Z
LN
 amounts to R
i
 = 2 · R
L
2) Measurement:  Z
L-PE
 amounts to R
ELoop 
3) Calculation: 
R
E1
 amounts to Z
L-PE
 – 1/2 · Z
L-N
; where R
B
 = 0
The value for operational earth conductor resistance R
B
 should be 
ignored in the calculation of earthing resistance, because it is 
generally unknown.
The calculated earthing resistance thus includes operational earth 
conductor resistance as a safety factor.
In parameter setting   steps 1 to 3 are performed auto-
matically by the test instrument. 
Select Measuring Function
Select Operating Mode
Set Parameters
❑ Measuring range: AUTO, 10 kΩ (4 mA), 1 kΩ (40 mA), 100 Ω 
(0.4 A), 10 Ω (3.7 ... 7 A). In systems with RCCBs, resistance 
or test current must be selected such that it is less than trip-
ping current (½ I
ΔN
).
❑ Connection type: 2-pole adapter
❑ Contact voltage: UL < 25 V, < 50 V, < 65 V
❑ Test current waveshape: Sinusoidal (full-wave), 15 mA sinusoidal 
(full-wave), DC offset and positive half-wave
❑ System type: TN/TT, IT
❑ Transformer ratio: irrelevant in this case
Start Measurement 
P
R
O
F
I
T
E
S
T
Ri
W
a
t
e
r
P
i
p
e
E
2
E
1
B
R
E
Limit value:
R
E
 > Limit Value
U
L
 ⏐ R
L