User Manual
GMC-I Messtechnik GmbH 23
7.3 Testing for Special RCDs
7.3.1 System, Type RCD-S Selective RCCBs
Selective RCDs are used in systems which include two series 
connected RCCBs which are not tripped simultaneously in the 
event of a fault. These selective RCDs demonstrate delayed 
response characteristics and are identified with the   symbol.
Measuring Method
The same measuring method is used as for standard RCCBs (see 
sections 7.1 on page 19 and 7.2.1 on page 21).
If selective RCDs are used, earthing resistance may not exceed 
half of the value for standard RCCBs.
For this reason, the instrument displays twice the measured value 
for contact voltage.
Select Measuring Function
Set Parameter – Selective 
Start Measurement 
Tripping Test
➭ Press the I
ΔN
 key. The RCCB is tripped. Blinking bars appear 
at the display panel, after which time to trip t
A
 and earthing re-
sistance R
E
 are displayed.
The tripping test need 
only be performed at 
one measuring point for 
each RCCB.
Note
Selective RCDs demonstrate delayed response charac-
teristics. Tripping performance is briefly influenced (up to 
30 s) due to pre-loading during measurement of contact 
voltage. In order to eliminate pre-charging caused by the 
measurement of contact voltage, a waiting period must 
be observed prior to the tripping test. After the measuring 
sequence has been started (tripping test), blinking bars 
are displayed for approximately 30 seconds. Tripping 
times of up to 1000 ms are allowable. The tripping test is 
executed immediately after once again pressing the I
ΔN
key.
7.3.2 PRCDs with Non-Linear Type PRCD-K Elements
The PRCD-K is a portable RCD with electronic residual current 
evaluation laid out as an in-line device which switches all poles (L, 
N and PE). An undervoltage trigger and protective conductor 
monitoring are additionally integrated into the PRCD-K.
The PRCD-K is equipped with an undervoltage trigger, for which 
reason it has to be operated with line voltage, and measurements 
may only be performed in the on state (PRCD-K switches all 
poles).
Terminology (from DIN VDE 0661)
Portable protective devices are circuit breakers which can be con-
nected between power consuming devices and permanently 
installed electrical outlets by means of standardized plug-and-
socket devices.
A reusable, portable protective device is a protective device which 
is designed such that it can be connected to movable cables.
Please be aware that a non-linear element is usually integrated 
into PRCDs, which leads to immediate exceeding of the greatest 
allowable contact voltage during U
IΔ
 measurements (U
IΔ
 greater 
than 50 V).
PRCDs which do not include a non-linear element in the protec-
tive conductor must be tested in accordance with section 7.3.3 
on page 24.
Objective (from DIN VDE 0661)
Portable residual current devices (PRCDs) serve to protect per-
sons and property. They allow for the attainment of increased lev-
els of protection as provided by protective measures utilized in 
electrical systems for the prevention of electrical shock as defined 
in DIN VDE 0100, part 410. They are to be designed such that 
they can be installed by means of a plug attached directly to the 
protective device, or by means of a plug with a short cable.
S
I
ΔN
I
F
or
Type 1: 










