Measuring Method
The following can be measured, depending upon the measuring 
method:
•Time to trip t
A
: tripping test with nominal residual current I
ΔN
(The PRCD-K must be tripped at 50% nominal current.)
• Tripping current I
Δ
: testing with rising residual current I
F
Select Measuring Function
Connection 
Set the Parameter – PRCD with Non-Linear Elements 
Start Measurement 
7.3.3 SRCD, PRCD-S (SCHUKOMAT, SIDOS or comparable)
RCCBs from the SCHUKOMAT SIDOS series, as well as others 
which are of identical electrical design, must be tested after 
selecting the corresponding parameter. 
Monitoring of the PE conductor is performed for RCDs of this 
type. The PE conductor is monitored by the summation current 
transformer. If residual current flows from L to PE, tripping current 
is cut in half, i.e. the RCCB must be tripped at 50% nominal resid-
ual current I
ΔN
.
Whether or not PRCDs and selective RCDs are of like design can 
be tested by measuring contact voltage U
IΔN
. If a contact voltage 
U
IΔN
 of greater than 70 V is measured at the PRCD of an other-
wise error-free system, the PRCD more than likely contains a non-
linear element.
PRCD-S
The PRCD-S (portable residual current device – safety) is a spe-
cial, portable, protective device with protective conductor detec-
tion or protective conductor monitoring. The device serves to pro-
tect persons from electrical accidents in the low-voltage range 
(130 to 1000 V). The PRCD-S must be suitable for commercial 
use, and is installed like an extension cable between an electrical 
consumer – as a rule an electrical tool – and the electrical outlet.
Select Measuring Function
Set Parameter – SRCD / PRCD 
Start Measurement 
I
ΔN
I
F
or
Type 1: 
I
ΔN
I
F
or
Type 1: 