7.4 Testing Residual Current Circuit Breakers in TN-S Systems
Connection 
RCCBs can only be used in TN-S systems. An RCCB would not 
work in a TN-C system because PE is directly connected to the 
neutral conductor in the outlet (it does not bypass the RCCB). 
This means that residual current would be returned via the RCCB 
and would not generate any differential current, which is required 
in order to trip the RCCB.
As a rule, the display for contact voltage is also 0.1 V, because 
the nominal residual current of 30 mA together with minimal loop 
resistance results in a very small voltage value:
7.5 Testing of RCD Protection in IT Systems with High Cable 
Capacitance (e.g. in Norway)
The desired system type (TN/TT oder IT) can be selected for RCD 
test type U
IΔN
 (I
ΔN
, t
a
), and for earthing measurement (R
E
).
A probe is absolutely essential for measurement in IT systems, 
because contact voltage U
IΔN
 which occurs in these systems 
cannot otherwise be measured.
After selecting the IT system setting, connection with probe is 
selected automatically.
Set the Parameter – Select System Type 
Start Measurement 
UIΔNR
E
IΔN• 1Ω 30mA⋅ 30mV 0
·
03V,== ==
System 
type: