8.1.1 Measurement with Positive Half-Waves 
(only MTECH+/MXTRA/SECULIFE IP)
Measurement by means of half-waves plus direct current makes it 
possible to measure loop impedance in systems which are 
equipped with RCCBs.
For DC measurement with half-waves you can choose between 
two alternatives:
DC-L:  lower premagnetization current allowing for faster mea-
surement
DC-H: higher premagnetization current, therefore higher protec-
tion against tripping of RCD
Select Measuring Function
Set Parameters 
* Parameters used for report generation only which do not influence the measurement
Sine (full wave)  Setting for electric circuits without RCD
15 mA sinusoidal  Setting only for motor protection switch
with low nominal current
DC+half-wave  Setting for electric circuits with RCD
Start Measurement 
Semiautomatic
Measurement
8.2 Evaluation of Measured Values
The maximum allowable 
loop impedance Z
L-PE
which may be displayed 
after allowance has 
been made for maxi-
mum operating mea-
surement error (under 
normal measuring con-
ditions) can be deter-
mined with the help of 
Table 1 on page 92. 
Intermediate values can 
be interpolated.
The maximum allowable 
nominal current for the 
protective device (fuse 
or circuit breaker) for a line voltage of 230 V after allowance has 
been made for maximum measuring error can be determined with 
the help of Table 6 on page 93 based upon measured short-cir-
cuit current (corresponds to DIN VDE 0100 Part 600).
Special Case: Suppressing Display of the Limit Value
The limit value cannot be 
ascertained. The inspec-
tor is prompted to evalu-
ate the measured val-
ues himself, and to 
acknowledge or reject 
them with the help of the 
softkeys.
Measurement passed: 
key 
✔
Measurement failed: 
X key
The measured value can 
only be saved after it has 
been evaluated.
Z
L-PE
Tripping characteristics:
Diameter*: 1.5 to 70 sq. mm
Cable types*: NY...- H07...
Number of wires*: 2 to 10-strand
Nominal current: 
2 ... 160 A, 9999 A
A, B/L, C/G, D, E, H, K, GL/GG & Factor
Sine
15 mA sinusoidal
Waveform:
DC-L offset and positive half-wave
Contact voltage:
DC-H offset and positive half-wave
2-pole 
Measurement with country-specific
plug insert (e.g. Schuko)
Note
Selecting test probe and Lx-PE 
reference or AUTO is only relevant for 
report generation.
Semiautomatic measurement
See also section 5.8 regarding the 
AUTO parameter.
Polarity selection
measurement 