8.3 Settings for Short-circuit current Calculation – Parameter I
K
Short-circuit current I
K
 is used to test shutdown by means of an 
overcurrent protective device. In order for an overcurrent protec-
tive device to be tripped on time, short-circuit current I
K
 must be 
greater than tripping current Ia (see table 6 in section 21.1). The 
variants which can be selected with the “Limits” key have the fol-
lowing meanings:
I
K
: Ia The measured value displayed for I
K
 is used without 
any correction to calculate Z
L-PE
.
I
K
: Ia+Δ% The measured value displayed for Z
L-PE
 is corrected 
by an amount equal to the test instrument’s measuring 
uncertainty in order to calculate I
K
.
I
K
: 2/3 Z In order to calculate I
K
, the measured value displayed 
for Z
L-PE
 is corrected by an amount corresponding to 
all possible deviations (these are defined in detail by 
VDE 0100, part 600, as Z
s(m)
 ≤ 2/3 x U
0
/Ia).
I
K
: 3/4 Z Z
s(m)
 ≤ 3/4 x U
0
/Ia
Z Loop impedance
I
K
Short-circuit current
U Voltage at the test probes, “U
N
” is displayed if voltage Umax. 
deviates from nominal voltage by 10%
f Frequency of the applied voltage, 
“f
N” is displayed if frequency fmax. deviates from nominal fre-
quency by 1%
Ia Tripping current (see data sheet for circuit breakers / fuses)
Δ
%
Test instrument inherent error
9 Measuring Line Impedance (Z
L-N
 function)
Measuring Method (internal line resistance measurement)
Supply impedance Z
L-N
 is measured by means of the same 
method used for loop impedance Z
L-PE 
(see section 8 on page 
27). However, the current loop is completed via neutral conductor 
N rather than protective conductor PE as is the case with loop 
impedance measurement.
Select Measuring Function
Connection: 
Schuko 
Connection: 
2-Pole Adapter 
Set Parameters
Press the softkey shown at the left in order to switch 
back and forth between the country-specific plug 
insert, e.g. SCHUKO, and 2-pole adapter. The 
selected connection type is displayed inversely 
(white on black).
Limit value:
I
K
 < limit value
U
L
 ⏐ R
L
Z
L-N
Nominal current: 
Diameter: 1.5 to 70 sq. mm
Cable types: NY..., H07...
Number of wires: 2 ... 10-strand
2 ... 160 A,  9999 A
Tripping characteristics:
A, B/L, C/G, D, E, H, K, GL/GG & Factor