10.1 Earthing Resistance Measurement – Mains Operated
The following types of measurement or connection are possible:
•   2-pole measurement via 2-pole adapter 
•  2-pole measurement via earthing contact plug 
(not possible in IT systems)
•   3-pole measurement via 2-pole adapter and
probe
•   Selective measurement: 2-pole measurement
with probe and current clamp sensor 
At left in figure:
2-pole measuring 
adapter for con-
tacting PE and L 
measuring points
At right in figure:
The PRO-Schuko 
measuring 
adapter can be 
used as an alter-
native.
Select Measuring Function
Select Operating Mode
The selected operating mode is displayed inversely: 
mains~ in white against a black background.
Special Case: Manual Measuring Range Selection (test current 
selection)
(R ≠ AUTO, R = 10 kΩ (4 mA), 1 kΩ (40 mA), 100 Ω (0.4 A), 
10 Ω (3.7 ... 7 A), 10 Ω/U
E
)
Note
When the measuring range is selected manually, accuracy val-
ues are only valid starting at 5% of the upper limit range value 
(except for the 
10
Ω
 range; separate display for small values).
Set Parameters
❑ Measuring range: AUTO, 10 kΩ (4 mA), 1 kΩ (40 mA), 100 Ω 
(0.4 A), 10 Ω (> 3.7 A) 
In systems with RCCBs, resistance or test current must be se-
lected such that it is less than tripping current (½ I
ΔN
).
❑ Contact voltage: UL < 25 V, < 50 V, < 65 V, see section 5.7 re-
garding freely selectable voltage.
❑ Transformer ratio: depends on utilized current clamp sensor
❑ Connection type: 2-pole adapter, 2-pole adapter + probe, 
2-pole adapter + clamp meter
❑ Type of system: TN or TT
❑ Test current waveform
See section 10.4 through section 10.6 regarding advisable parame-
ters for the respective measurement and connection types.
Perform Measurements
See section 10.4 through section 10.6.
10.2 Earthing Resistance Measurement – Battery Powered 
(only MPRO & MXTRA)
The 5 following types of measurement or connection are possible:
•  3-Pole measurement via PRO-RE adapter 
•  4-Pole measurement via PRO-RE adapter 
•  Selective measurement with clamp meter 
(4-pole) via PRO-RE adapter 
•  2-clamp measurement via PRO-RE/2 adapter
•  Measurement of soil resistivity 
ρ
E
via PRO-RE adapter 
Figure at right: 
PRO-RE adapter for connect-
ing earth electrode, auxiliary 
earth electrode, probe and 
auxiliary probe to the test 
instrument for 
3/4-pole measurement, 
selective measurement and 
measurement of soil resistivity
Figure at right: 
PRO-RE/2 measuring adapter as 
accessory for connecting the E-
Clip 2 generator clamp for 2-clamp 
measurement and earth loop resis-
tance measurement.
Select Measuring Function
Select Operating Mode
The selected operating mode is displayed inversely: 
white battery icon against black background.
Set Parameters
❑ Measuring range: AUTO, 50 kΩ, 20 kΩ, 2 kΩ, 200 Ω, 20 Ω 
❑ Current clamp sensor transformer ratio: 
1:1 (1 V/A,) 1:10 (100 mV/A), 1:100 (10 mV/A), 1:1000 (1 mV/A)
❑ Connection type: 3-pole, 4-pole, selective, 2-clamp, ρ
E
 (Rho)
❑ Distance d (for measuring 
ρ
E
): xx m
See section 10.7 through section 10.11 regarding advisable 
parameters for the respective measurement and connection 
types.
Perform Measurements
See section 10.7 through section 10.11.
R
E
R
E