User guide

Guideline Explanation/comment
Make sure that the space around the pump is
sufficient.
This facilitates ventilation, inspection, maintenance,
and service.
If you require lifting equipment such as a hoist or
tackle, make sure that there is enough space above
the pump.
This makes it easier to properly use the lifting
equipment.
Protect the unit from weather and water damage
due to rain, flooding, and freezing temperatures.
This is applicable if nothing else is specified.
Do not install and operate the equipment in
closed systems unless the system is constructed
with properly-sized safety devices and control
devices.
Acceptable devices:
Pressure relief valves
Compression tanks
Pressure controls
Temperature controls
Flow controls
If the system does not include these devices, consult
the engineer or architect in charge before you operate
the pump.
Take into consideration the occurrence of
unwanted noise and vibration.
The best pump location for noise and vibration
absorption is on a concrete floor with subsoil
underneath.
Concrete foundation requirements
Requirements
Make sure that you meet these requirements when you prepare the pump foundation:
The foundation must be able to absorb any vibration.
The foundation must be able to form a permanent and rigid support for the pumping unit.
The foundation must be of adequate strength to support the complete weight of the pump and driver,
plus the weight of the liquid that passes through it.
There should be at least 0.5 in.(12.7 mm) clearance between the sides of the pump and any portion of
the pit.
Typical installation
A typical installation has these characteristics:
Bolts with a pipe sleeve that is two and a half times the size of the bolt diameter embedded in the concrete
Properly sized
Installation (Continued)
Model 3171 Installation, Operation, and Maintenance Manual 17