User's Manual

Alarm Troubleshooting
313882C 83
E-9: MIX_IN_SETUP_ALARM
Cause Solution
Attempt to operate system while in Setup mode. System must be in Standby to change current recipe,
and cannot be operated.
E-10: REMOTE_STOP_ALARM
Cause Solution
Automation has requested that the system abort all oper-
ations.
Abort operations. Troubleshoot automation system.
E-11: PURGE_VOLUME_ALARM
Cause Solution
ProMix 3KS solvent flow switch is not activated while
purging.
Verify that the gun is not shut off and that the solvent flow
switch is activated while purge is taking place.
Minimum flush volume is set too high. Increase solvent supply or decrease minimum volume
setting.
No meter pulses during Color/Catalyst Dump. Color change solvent supply not set up or functional.
Check Color Change setup.
Table 10. Alarm Troubleshooting