User's Manual

Appendix B - ADM Setup Screens Overview
3A2175A 65
Auto Full-Volume
The low level sensor will initiate an automatic
refill when it does not see material
Automatic refill will continue until either the high
level sensor sees material or until the refill
time-out expires
The low level alarm will clear when the condition
clears
A button is provided to the user on the run
screens to instigate an automatic refill operation
at any time, this button can also be used to
abort a refill operation
If a refill setting other than Disabled is selected, the user
must set at least two level sensor locations as installed
by checking the check box on the screen. If all three
locations are set to installed, the system will default to
the Auto-Top Off refill setting and operate as follows:
The low level sensor will generate a low level alarm.
The high level sensor will generate a high level devi-
ation and abort any automatic refill operation.
When the middle sensor is not satisfied, automatic
refill will begin and will run until either the middle
sensor is satisfied, the high level sensor generates a
deviation (if the middle sensor fails), or the refill
time-out expires.
The low level alarm and the high level deviation will
clear when the condition clears.
A button is provided to the user on the Run screens
to instigate an automatic refill operation at any time.
This button can also be used to abort a refill opera-
tion.
The refill time-out setting may be set by the user as a
means to abort the refill in the case of a high level sen-
sor failure. When an automatic refill begins, the time-out
counter will begin to count down. If the timer expires
before the high level sensor is satisfied, the refill will
abort.
Conditioning Screen 1
This screen allows the user to select which temperature
conditioning components are installed in the system.
Check the box next to the component type for the appro-
priate side of the system to indicate that a component is
installed. A maximum of four components may be
selected.