User's Manual
Setup
14 3A2960D
1. Use the UP or DOWN ARROW
until LL:02 displays. This will set
the controller up to use a "pad-
dle-style" low level algorithm (like
the Graco G3 grease units). To
ensure a low level condition has
been met in this mode, 10 consec-
utive low level triggers must be
detected. If a low level trigger is
not detected in 30 seconds of run
mode, the count is reset to zero.
2. Press the ENTER button.
NOTE: When the user exits SETUP
MODE:
• An alarm sounds briefly and LED lights indicating
the new programming settings and OFF TIME infor-
mation are saved.
• The display shows the revision level.
• The controller goes to the beginning of a PUMP
OFF Cycle.
Operation
Run Mode
The controller is in Run Mode providing the following cir-
cumstances are present:
• The controller is not in SETUP MODE.
• An Alarm is not active.
Pressure Mode: Pump ON
The display indicates the amount of backup time
remaining (see Pressure Mode (on:Pr) ON setup, page
12).
• The Pressure ON LED illuminates and the pump
output is enabled as long as the system is in the
Pump ON state.
• If the pressure switch input is activated before the
Backup Pump On Time expires, the system
switches to a Pump OFF state.
• If the pressure switch is NOT activated before the
Backup Pump On Time expires the system faults,
goes to the Pump OFF state and pauses until the
alarm is cleared.
• Pump ON time is shown in MM:SS (minutes:sec-
onds)
Pressure Mode: Pump OFF
The display indicates the amount of time remaining in
the pump OFF cycle, counting down the Pump OFF time
value (see Programming OFF Time Duration, page 12).
• The pump output is disabled during the Pump OFF
time.
• The Time OFF LED is illuminated as long as the
system is in the Pump OFF state.
• Pump OFF time is shown in HH:MM (hours:minutes)
or MM:SS if the time remaining is less than an hour.